Brand: Lumel
Lumel RP3 Three-Phase Thyristor Power Controller 40-450 A
Description
The Lumel RP3-3-8 is a three-phase thyristor power controller rated 125 A on a 3 x 400 V, 50 Hz load circuit. It switches resistive and resistive-inductive loads without contacts and is built for electric heating: furnaces, extruder barrels, dryers and tube heaters. The same RP3 family covers 40, 70, 125, 200, 300 and 450 A, and the ordering code RP3-3-8 is the example printed by Lumel for the 125 A version without extra quality requirements.
Why thyristor control instead of contactors
A contactor wears when it switches a heater thousands of times, and its on-off action makes the process temperature swing. The RP3 replaces it with thyristors that modulate the power delivered to the load according to the control signal: phase-angle control, impulse (burst) control or simple on-off. The manual lists applications such as annealing and hard-soldering furnaces, crucible furnaces and smelters, plastics extruders, spring winding and tempering, spot and seam welders, infrared drying, glass production and chemical and petroleum preheating and tube-facing heaters.
Key features from the data sheet
- Contactless switching of resistive and inductive loads, up to 450 A in the family.
- Phase, impulse and on-off control, with a choice of impulse, continuous or potentiometric input.
- Soft-start trigger delay, control of the initial trigger angle and load current limitation.
- Trigger stoppage by an external signal.
- Signalling of incorrect phase sequence and of blown fuses.
- Two alarm relay outputs, one for fuse damage, control error or wrong supply connection and one for stop or over-temperature.
Technical specification
Power circuit by current range (manual, Table 2)
| Code / rating | Load power, lost power, fuse |
|---|---|
| RP3-1, 40 A | 30 kW; lost power in thyristors below 200 W; fuse 50 A (50FE Bussmann); I2t 440 A2s |
| RP3-2, 70 A | 53 kW; below 350 W; fuse 100 A (100FE); 3600 A2s |
| RP3-3, 125 A (this code) | 95 kW; below 600 W; fuse 160 (200) A (200FEE); 9600 A2s |
| RP3-4, 200 A | 152 kW; below 950 W; fuse 250 A (250FM); 28500 A2s |
| RP3-5, 300 A | 229 kW; below 1500 W; fuse 350 A (350FM); 68500 A2s |
| RP3-6, 450 A | 343 kW; below 2200 W; fuse 500 A (500FMM); 180000 A2s |
Control, supply and environment
| Parameter | Specification |
|---|---|
| Load circuit voltage | 3 x 400 V a.c., 50 Hz (for the load circuit rating of all codes) |
| Load type | Resistance or resistance-inductance load to EN 60947-4-2 and EN 60947-4-3 |
| Control inputs | Potentiometric 0 to 10 kohm; impulse 0/4 to 32 V (Rin 20 kohm); voltage 0 to 5 V (20 kohm) or 0 to 10 V (40 kohm); current 0 to 20 mA or 4 to 20 mA (125 ohm) |
| Control supply (UWB) | 195 to 253 V a.c., 50 Hz, 8 VA |
| Minimum input current | 1% of the controller output current range |
| Leakage current | 20 mA |
| Soft-start time | 0 to 10 s for phase or on-off control (set with the S-START potentiometer) |
| Span adjustment | Input gain 50 to 100% of the control signal |
| Alarm relays PK1 / PK2 | 60 mA, 350 V, Ron 35 ohm, isolation 1500 V r.m.s. |
| STOP signal input | 4 to 32 V, 5 mA |
| Ambient / storage temperature | 0 to 40 degrees C / -25 to 55 degrees C |
| Humidity and position | Below 90% without condensation; vertical operating position |
| Dimensions | 212 x 318 x 177 mm (40, 70, 125 A); 383 x 433 x 281 mm (200, 300, 450 A) |
| Weight | 8.5 kg (40, 70, 125 A); 37 kg (200, 300, 450 A) |
| Protection / safety | IP00 to EN 60529; pollution degree 2; installation category III; 320 V phase-to-earth on power and supply circuits |
| Terminal wiring | 40 A: 16 mm2; 70 A: 25 mm2; 125 A: 50 mm2; 200, 300, 450 A: busbar 100, 200, 300 mm2 |
Reading the RP3 ordering code
The code has the form RP3 – X – X. The first digit sets the maximum output current: 1 for 40 A, 2 for 70 A, 3 for 125 A, 4 for 200 A, 5 for 300 A and 6 for 450 A, all for a 3 x 400 V a.c., 50 Hz load circuit. The last character is the acceptance test: 8 without extra quality requirements, 7 with an extra quality inspection certificate and X for other requirements agreed with the manufacturer. So RP3-3-8 is the 125 A controller without the extra certificate. Choose the current range with margin above the heater current and size the semiconductor fuses to the table above.
Installation and operation notes from the manual
The IP00 enclosure means the controller is built into a cabinet or a protected enclosure and mounted vertically on a panel. The front carries six status LEDs (supply and readiness, load current, stop, error, over-temperature and fuse failure), three potentiometers for soft start, current limit and span, and a DIP switch for the input type and the control mode. Select the control type with the supply off. Control wiring on the LZ1 terminals takes 0.35 to 2.5 mm2. The fuses of the 40, 70 and 125 A versions are accessible after removing the protective cover. Thyristor heat loss (below 600 W for 125 A) must be removed by cabinet design.
Use in Gulf industrial heating
Heating loads in Omani and GCC plants, such as preheating of pipework, plastics extrusion, drying and furnace lines, run in hot switchrooms. The rated ambient of 0 to 40 degrees C limits where the unit can be installed without cabinet cooling, so allow for the losses and the local ambient when sizing the enclosure.
Frequently asked questions
What does RP3-3-8 mean?
RP3 three-phase power controller, range code 3 (125 A) for a 3 x 400 V load circuit, acceptance code 8 (no extra quality inspection certificate).
Which control signals can the RP3 accept?
Impulse 0/4 to 32 V, voltage 0 to 5 V or 0 to 10 V, current 0 to 20 mA or 4 to 20 mA and a potentiometer of 0 to 10 kohm.
Does the RP3 have a soft start?
Yes. The soft-start time is adjustable from 0 to 10 s for phase or on-off control.
What fuse does the 125 A version need?
The manual lists a 160 (200) A fuse, for example Bussmann 200FEE.
What load types is it intended for?
Resistance and resistance-inductance loads, according to the manual.
Documents and quotation
To buy the Lumel RP3-3-8 through Seven Star LLC, send an enquiry that states the exact code and quantity. We act as an independent supplier in Muscat and reply with delivery time and terms. The Lumel RP3 user manual is attached. It covers wiring, the control types, the fuse table and the ordering codes used on this page; data sheet RP3-19A repeats the ordering example. Read the maker documents first if you need to verify a figure. Related items: Electrical & Power.
Datasheets & Documents
- Manual RP3 three-phase power controller user manual (Lumel) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Lumel is a Polish manufacturer of industrial measuring and automation devices based in Zielona Góra, known under this name since 1953. Its catalogue covers power network meters and analyzers, digital panel meters, controllers, recorders, transducers, current transformers and shunts.
Seven Star LLC is an independent supplier in Muscat. We list Lumel instruments, each with the manufacturer document, for switchboard builders and plant engineers in Oman and the GCC.
Lumel product series
Power measurement includes the N14 and ND20 three-phase power network meters with RS-485, the N43 DIN rail meter, the N100 network analyzer with Ethernet and the N32H digital DC circuit meter. The NF20 is a power factor controller for 4 to 12 capacitor steps.
Process instruments include the N31U universal digital panel meter, the RE82 PID temperature controller in 48 x 96 mm format, the RP3 three-phase thyristor power controller from 40 to 450 A and the HT20 Ethernet temperature and humidity monitor with PoE.
Where Lumel instruments are used
Switchboards and distribution panels, generator and capacitor bank panels, battery and rectifier circuits, industrial heating, plastics and food processing lines, and monitored storage and server rooms, wherever readings must reach a PLC, SCADA or building system.
Ordering Lumel instruments: what we need
Send the full ordering code, which defines inputs, supply voltage and communication, or give the measured quantities, CT and VT ratios, supply voltage, output and interface required.
Browse Lumel products by category: Power Meters & Power Quality.
Related products
Frequently Asked Questions
RP3 three-phase power controller, range code 3 (125 A) for a 3 x 400 V load circuit, acceptance code 8 (no extra quality inspection certificate).
Impulse 0/4 to 32 V, voltage 0 to 5 V or 0 to 10 V, current 0 to 20 mA or 4 to 20 mA and a potentiometer of 0 to 10 kohm.
Yes. The soft-start time is adjustable from 0 to 10 s for phase or on-off control.
The manual lists a 160 (200) A fuse, for example Bussmann 200FEE.
Resistance and resistance-inductance loads, according to the manual.