Brand:

DAB FEKA VS GRINDER 1000 MA Sewage Pump with Shredder

Description

FEKA VS GRINDER 1000 MA is the automatic single-phase version of the DAB FEKA VS GRINDER: a submersible sewage pump with a stainless steel shredder, a vortex cast-iron impeller, 25 m maximum head, up to 14.4 m3/h and a pump certified to EN 12050-1 according to the sheet.

Shredding sewage into small-bore discharge lines

The FEKA VS GRINDER is described by DAB as a submersible pump for draining wastewater in commercial building service. Its shredder cuts the solids so the discharge can run through small-diameter pipes or against high pressures, which is the reason to choose a grinder pump instead of an open-vortex sewage pump when the rising main is narrow or long. The sheet states it is certified to EN 12050-1, the European standard for lifting systems for wastewater containing faecal matter in buildings and on construction sites.

The code ends in MA: the datasheet lists the 1000 MA (single-phase, automatic with an integrated float switch), the 1000 M-NA (single-phase, manual, no float) and the 1000 TNA (three-phase, manual). The 1000 MA starts and stops itself on the level of the tank, so it can run unattended in a collection pit.

Features listed by DAB

  • Vortex impeller in cast iron with a stainless steel cutter and cutter base; the shredding system is AISI 630 stainless steel.
  • Pump housing and base in cast iron; motor case, cap, seal-holder cover and handle in stainless steel.
  • Double mechanical seal with an oil chamber: silicon carbide against silicon carbide on the pump side, carbon/alumina on the motor side; AISI 316 shaft.
  • Motor cooled by the pumped liquid, on oversized greased-for-life ball bearings.
  • Thermo-amperometric protection with the capacitor fitted as standard on the single-phase version.
  • Outlet horizontal as standard, vertical with the curve kit accessory.

Technical specification

Application data (FEKA VS GRINDER)

Parameter Specification
Flow rate 0 to 14.4 m3/h
Maximum head 25 m
Pumped liquid Sewage water, grey water
Liquid temperature 0 to +40°C for domestic use
Outlet 1 1/2 inch gas thread, DN32 and DN40
Motor protection / insulation IP 68 / thermal class F
Installation Fixed or mobile, vertical position
Maximum immersion depth 7 m
Power cable H07RN8-F

FEKA VS GRINDER 1000 MA electrical and hydraulic data

Parameter Specification
Supply 1 x 220-240 V ~, 50 Hz
P1 max / P2 nominal 1.3 kW / 1 kW (1.3 HP)
Rated / starting current 6.4 A / 29.9 A
Capacitor 35 µF, 450 V
Head at 0 / 2 / 4 m3/h 25 m / 23 m / 21 m
Head at 6 / 8 / 10 m3/h 18 m / 14.5 m / 10.5 m
Head at 12 / 14 m3/h 6.5 m / 0.67 m

Dimensions and weight (FEKA VS GRINDER 1000)

Parameter Specification
A / B / H / H1 253 / 209 / 496 / 87 mm
Outlet Rp 1 1/2 inch thread, or DN32 PN10/6 and DN40 PN6 flange as printed
Packing L/A x L/B x H 290 x 230 x 560 mm
Packing volume 0.037 m3
Weight 23 kg

Materials

Parameter Specification
Pump housing, pump base, impeller Cast iron
Cutter, cutter base, seal disc, motor flange, motor case Stainless steel
Lower and upper bearing supports Aluminium
Cable glands Nickel-plated brass
O-rings NBR
Float cable H07RN-F

MA, M-NA or TNA

Choose the 1000 MA when you want the pump to start from its integrated float and have a single-phase supply. The 1000 M-NA is the same pump without the float, for use with an external level controller, and the 1000 TNA is the three-phase 380-415 V version (3 A, 1 kW), also without float. All three share the same hydraulic curve, so choose on supply and control, not on duty. The sheet lists the curve for a 1 mm2/s viscosity, 1000 kg/m3 density liquid; thicker sewage will reduce performance.

Installation

The pump can be fixed on a coupling device or stand directly on the tank bottom as a mobile unit, always vertical, to a maximum immersion depth of 7 m. For a vertical discharge you need the curve kit accessory. Use H07RN8-F supply cable and keep the float free to swing inside the pit. Connect the three-phase thermal protection to a control panel; the single-phase version has its own protection.

Typical uses around Oman

Hotel and apartment basements, restaurant and kitchen blocks, labour-camp toilets and below-grade bathrooms that cannot drain by gravity need a lifting station, and a shredder pump lets the contractor use a small-bore pressure main. Always size the pit and ventilate it according to the local drainage code, and confirm that your sewage does not contain wipes or plastics beyond what the shredder is designed to cut.

Selection and installation notes

A sewage pump is selected from the type of waste, the head and the pit size. Use a pit with a level control and an alarm, fit a non-return valve and isolating valve on the discharge, keep the discharge pipe size no smaller than the pump outlet and avoid sharp bends. Do not discharge rags, plastics or building waste, and lift the pump for inspection and cleaning at regular intervals.

Information needed for a quotation

Send the full model code, the quantity, the delivery location in Oman or the GCC, the intended use and any accessories needed, so that the complete package can be quoted together.

Documents and supply information

The manufacturer data sheet is attached to this page and should be read together with the project specification and the site risk assessment before a purchase is confirmed. Ratings, standards and dimensions are quoted as printed on that sheet. Lead time, stock position and certificates available with the shipment are confirmed in the quotation, and we supply to Oman and the wider GCC region for industrial, utility and building services projects.

Related DAB items

DAB also lists the FEKA VS, FEKA BVP and FEKAFOS series in the same catalogue for other sewage duties. Control panels, level switches and curve kits are accessories and not part of this code. See other DAB pumps in the Pumps category.

Frequently asked questions

What does the MA suffix mean?

It marks the single-phase automatic version with an integrated float switch; M-NA is manual without float.

What is the maximum head and flow?

25 m maximum head and up to 14.4 m3/h, per the datasheet.

Is the pump certified for sewage?

The sheet states certification to EN 12050-1 for lifting systems for wastewater containing faecal matter in buildings and construction sites.

How deep can it be immersed?

Maximum immersion depth is 7 metres, with IP 68 motor protection.

Does Seven Star LLC act as a DAB Pumps distributor?

No. Seven Star LLC is an independent supplier in Muscat that sources DAB Pumps products on request.

Documents and quotation

This page carries the official DAB Pumps technical data sheet for FEKA VS GRINDER 1000 MA. Seven Star LLC is an independent supplier in Muscat and sources DAB Pumps products on request; tell us the quantity and delivery point to receive a quotation. Always confirm the order code and technical values in the document first. See more in the product category.

Datasheets & Documents
  • PDF Datasheet DAB FEKA VS GRINDER technical sheet (PDF) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

DAB Pumps is an Italian pump maker founded in 1975 and based in Mestrino, Padua. It produces pumps and pressure boosting systems for domestic, building, irrigation and light industrial water.

Seven Star LLC is an independent supplier in Muscat. We list DAB pumps and booster sets for homes, buildings and contractors in Oman and the GCC.

DAB product series

Boosting pumps include the ESYBOX MINI 3 electronic pressure booster and the 2NKV 10/8 T twin-pump booster set with two 3 kW pumps. Surface pumps include the JET 102 M self-priming pump, the K 35/40 M twin-impeller pump, the KDN 50-160 standardised end-suction pump and the KLP 50-1200 T in-line circulator.

Submersible pumps include the S4 8/9 4-inch borehole pump, the MICRA 100 M 3-inch multi-impeller pump, the DRENAG 1000 M stainless drainage pump and the FEKA VS GRINDER 1000 MA sewage pump with shredder.

Where DAB pumps are used

Water pressure in villas and buildings, tank transfer, wells and boreholes, heating and cooling circulation, garden irrigation, and drainage and sewage lifting.

Ordering DAB pumps: what we need

Send the model, or the flow, head and liquid, the power supply (single or three-phase) and the installation, such as a tank, well size or sump.

Frequently Asked Questions

What does the MA suffix mean?
It marks the single-phase automatic version with an integrated float switch; M-NA is manual without float.
What is the maximum head and flow?
25 m maximum head and up to 14.4 m3/h, per the datasheet.
Is the pump certified for sewage?
The sheet states certification to EN 12050-1 for lifting systems for wastewater containing faecal matter in buildings and construction sites.
How deep can it be immersed?
Maximum immersion depth is 7 metres, with IP 68 motor protection.
Does Seven Star LLC act as a DAB Pumps distributor?
No. Seven Star LLC is an independent supplier in Muscat that sources DAB Pumps products on request.