Brand: DAB Pumps
DAB FEKA VS GRINDER 1000 MA Sewage Pump with Shredder
Description
FEKA VS GRINDER 1000 MA is the automatic single-phase version of the DAB FEKA VS GRINDER: a submersible sewage pump with a stainless steel shredder, a vortex cast-iron impeller, 25 m maximum head, up to 14.4 m3/h and a pump certified to EN 12050-1 according to the sheet.
Shredding sewage into small-bore discharge lines
The FEKA VS GRINDER is described by DAB as a submersible pump for draining wastewater in commercial building service. Its shredder cuts the solids so the discharge can run through small-diameter pipes or against high pressures, which is the reason to choose a grinder pump instead of an open-vortex sewage pump when the rising main is narrow or long. The sheet states it is certified to EN 12050-1, the European standard for lifting systems for wastewater containing faecal matter in buildings and on construction sites.
The code ends in MA: the datasheet lists the 1000 MA (single-phase, automatic with an integrated float switch), the 1000 M-NA (single-phase, manual, no float) and the 1000 TNA (three-phase, manual). The 1000 MA starts and stops itself on the level of the tank, so it can run unattended in a collection pit.
Features listed by DAB
- Vortex impeller in cast iron with a stainless steel cutter and cutter base; the shredding system is AISI 630 stainless steel.
- Pump housing and base in cast iron; motor case, cap, seal-holder cover and handle in stainless steel.
- Double mechanical seal with an oil chamber: silicon carbide against silicon carbide on the pump side, carbon/alumina on the motor side; AISI 316 shaft.
- Motor cooled by the pumped liquid, on oversized greased-for-life ball bearings.
- Thermo-amperometric protection with the capacitor fitted as standard on the single-phase version.
- Outlet horizontal as standard, vertical with the curve kit accessory.
Technical specification
Application data (FEKA VS GRINDER)
| Parameter | Specification |
|---|---|
| Flow rate | 0 to 14.4 m3/h |
| Maximum head | 25 m |
| Pumped liquid | Sewage water, grey water |
| Liquid temperature | 0 to +40°C for domestic use |
| Outlet | 1 1/2 inch gas thread, DN32 and DN40 |
| Motor protection / insulation | IP 68 / thermal class F |
| Installation | Fixed or mobile, vertical position |
| Maximum immersion depth | 7 m |
| Power cable | H07RN8-F |
FEKA VS GRINDER 1000 MA electrical and hydraulic data
| Parameter | Specification |
|---|---|
| Supply | 1 x 220-240 V ~, 50 Hz |
| P1 max / P2 nominal | 1.3 kW / 1 kW (1.3 HP) |
| Rated / starting current | 6.4 A / 29.9 A |
| Capacitor | 35 µF, 450 V |
| Head at 0 / 2 / 4 m3/h | 25 m / 23 m / 21 m |
| Head at 6 / 8 / 10 m3/h | 18 m / 14.5 m / 10.5 m |
| Head at 12 / 14 m3/h | 6.5 m / 0.67 m |
Dimensions and weight (FEKA VS GRINDER 1000)
| Parameter | Specification |
|---|---|
| A / B / H / H1 | 253 / 209 / 496 / 87 mm |
| Outlet | Rp 1 1/2 inch thread, or DN32 PN10/6 and DN40 PN6 flange as printed |
| Packing L/A x L/B x H | 290 x 230 x 560 mm |
| Packing volume | 0.037 m3 |
| Weight | 23 kg |
Materials
| Parameter | Specification |
|---|---|
| Pump housing, pump base, impeller | Cast iron |
| Cutter, cutter base, seal disc, motor flange, motor case | Stainless steel |
| Lower and upper bearing supports | Aluminium |
| Cable glands | Nickel-plated brass |
| O-rings | NBR |
| Float cable | H07RN-F |
MA, M-NA or TNA
Choose the 1000 MA when you want the pump to start from its integrated float and have a single-phase supply. The 1000 M-NA is the same pump without the float, for use with an external level controller, and the 1000 TNA is the three-phase 380-415 V version (3 A, 1 kW), also without float. All three share the same hydraulic curve, so choose on supply and control, not on duty. The sheet lists the curve for a 1 mm2/s viscosity, 1000 kg/m3 density liquid; thicker sewage will reduce performance.
Installation
The pump can be fixed on a coupling device or stand directly on the tank bottom as a mobile unit, always vertical, to a maximum immersion depth of 7 m. For a vertical discharge you need the curve kit accessory. Use H07RN8-F supply cable and keep the float free to swing inside the pit. Connect the three-phase thermal protection to a control panel; the single-phase version has its own protection.
Typical uses around Oman
Hotel and apartment basements, restaurant and kitchen blocks, labour-camp toilets and below-grade bathrooms that cannot drain by gravity need a lifting station, and a shredder pump lets the contractor use a small-bore pressure main. Always size the pit and ventilate it according to the local drainage code, and confirm that your sewage does not contain wipes or plastics beyond what the shredder is designed to cut.
Selection and installation notes
A sewage pump is selected from the type of waste, the head and the pit size. Use a pit with a level control and an alarm, fit a non-return valve and isolating valve on the discharge, keep the discharge pipe size no smaller than the pump outlet and avoid sharp bends. Do not discharge rags, plastics or building waste, and lift the pump for inspection and cleaning at regular intervals.
Information needed for a quotation
Send the full model code, the quantity, the delivery location in Oman or the GCC, the intended use and any accessories needed, so that the complete package can be quoted together.
Documents and supply information
The manufacturer data sheet is attached to this page and should be read together with the project specification and the site risk assessment before a purchase is confirmed. Ratings, standards and dimensions are quoted as printed on that sheet. Lead time, stock position and certificates available with the shipment are confirmed in the quotation, and we supply to Oman and the wider GCC region for industrial, utility and building services projects.
Related DAB items
DAB also lists the FEKA VS, FEKA BVP and FEKAFOS series in the same catalogue for other sewage duties. Control panels, level switches and curve kits are accessories and not part of this code. See other DAB pumps in the Pumps category.
Frequently asked questions
What does the MA suffix mean?
It marks the single-phase automatic version with an integrated float switch; M-NA is manual without float.
What is the maximum head and flow?
25 m maximum head and up to 14.4 m3/h, per the datasheet.
Is the pump certified for sewage?
The sheet states certification to EN 12050-1 for lifting systems for wastewater containing faecal matter in buildings and construction sites.
How deep can it be immersed?
Maximum immersion depth is 7 metres, with IP 68 motor protection.
Does Seven Star LLC act as a DAB Pumps distributor?
No. Seven Star LLC is an independent supplier in Muscat that sources DAB Pumps products on request.
Documents and quotation
This page carries the official DAB Pumps technical data sheet for FEKA VS GRINDER 1000 MA. Seven Star LLC is an independent supplier in Muscat and sources DAB Pumps products on request; tell us the quantity and delivery point to receive a quotation. Always confirm the order code and technical values in the document first. See more in the product category.
Datasheets & Documents
- Datasheet DAB FEKA VS GRINDER technical sheet (PDF) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
DAB Pumps is an Italian pump maker founded in 1975 and based in Mestrino, Padua. It produces pumps and pressure boosting systems for domestic, building, irrigation and light industrial water.
Seven Star LLC is an independent supplier in Muscat. We list DAB pumps and booster sets for homes, buildings and contractors in Oman and the GCC.
DAB product series
Boosting pumps include the ESYBOX MINI 3 electronic pressure booster and the 2NKV 10/8 T twin-pump booster set with two 3 kW pumps. Surface pumps include the JET 102 M self-priming pump, the K 35/40 M twin-impeller pump, the KDN 50-160 standardised end-suction pump and the KLP 50-1200 T in-line circulator.
Submersible pumps include the S4 8/9 4-inch borehole pump, the MICRA 100 M 3-inch multi-impeller pump, the DRENAG 1000 M stainless drainage pump and the FEKA VS GRINDER 1000 MA sewage pump with shredder.
Where DAB pumps are used
Water pressure in villas and buildings, tank transfer, wells and boreholes, heating and cooling circulation, garden irrigation, and drainage and sewage lifting.
Ordering DAB pumps: what we need
Send the model, or the flow, head and liquid, the power supply (single or three-phase) and the installation, such as a tank, well size or sump.
Browse DAB Pumps products by category: Pumps.
Related products
Frequently Asked Questions
It marks the single-phase automatic version with an integrated float switch; M-NA is manual without float.
25 m maximum head and up to 14.4 m3/h, per the datasheet.
The sheet states certification to EN 12050-1 for lifting systems for wastewater containing faecal matter in buildings and construction sites.
Maximum immersion depth is 7 metres, with IP 68 motor protection.
No. Seven Star LLC is an independent supplier in Muscat that sources DAB Pumps products on request.