Brand: Lumel
Lumel N100 21100M0 3-Phase Power Network Analyzer, Ethernet
Description
The Lumel N100 21100M0 is a 144 x 144 mm panel analyzer for three-phase, 3- or 4-wire networks with a bright four-line, two-colour LED display. This ordering code has 3 x 230/400 V voltage inputs, 1 A / 5 A current inputs, three relays, one analog output, a pulse input/output, RS-485 and Ethernet with an 8 GB internal archive. It reports harmonics up to the 51st and four-quadrant energy, so it serves feeders where a larger display and recorded data are wanted.
A large-format analyzer for main feeders
Where the 96 x 96 mm meters are too small to read from a distance, the N100 gives four lines of 4 1/2 digits, 14 mm high, with backlit units and up to 20 programmable display pages. It measures phase and line voltages, phase currents, active, reactive and apparent power per phase and in total, power factor and tan phi, frequency, THD of voltage and current and the harmonics of both, plus demand values for P, S and I over 15, 30 or 60 minutes. A pulse input lets it collect the readings of an external pulse-output meter, so one N100 can also sum a remote counter.
Key features from the data sheet
- Two-colour LED display (red, green) with backlit units and 20 configurable pages.
- Four-quadrant energy measurement and storage of minimum and maximum values.
- Configurable analog and alarm outputs, and a pulse output for active energy.
- RS-485 MODBUS and 10/100Base-T Ethernet with Modbus TCP/IP, HTTP and FTP servers, DHCP client.
- Archive in an 8 GB internal file system, with a battery-supported real-time clock.
Technical specification
Measured parameters and classes (data sheet)
| Quantity | Range and class |
|---|---|
| Current 1 A / 5 A | 1 A: 0.010 to 1.200 A; 5 A: 0.050 to 6.000 A (tr_I = 1); up to 20.00 kA with ratio; class 0.2 |
| Voltage L-N | 57.7 V: 5.7 to 70.0 V; 230 V: 23.0 to 276.0 V; 400 V: 40.0 to 480.0 V; class 0.2 |
| Voltage L-L | 100 V: 10.0 to 120.0 V; 400 V: 40.0 to 480.0 V; 690 V: 69.0 to 830.0 V; class 0.5 |
| Active power / apparent power | Class 0.5 per EN 61557-12 as printed |
| Reactive power / reactive energy | Class 2 |
| Active and apparent energy | Class 0.5 |
| Frequency | 45.00 to 65.00 to 500 Hz; class 0.2 (higher frequencies need phase voltages above 45% or 85% Un) |
| THD of voltage and current / harmonics | 0.0 to 100.0%; class 5 at 50/60 Hz; harmonics up to the 50th as printed in the table, 51st in the feature list |
| Transformer ratios | Current 1 to 10000; voltage 1 to 4000 |
Outputs, interface and construction
| Parameter | Specification |
|---|---|
| Analog output | 1 output 0 to 20 mA (4 to 20 mA) programmable, error 0.2%; versions with 3 outputs of -20 to 20 mA also exist |
| Relay outputs | 3 programmable, voltage-free NO contact, 250 V a.c. / 0.5 A a.c. |
| Pulse output / input | OC (NPN) passive, 18 to 27 V, for active energy; passive pulse input 0/12 to 36 V d.c. |
| RS-485 | MODBUS RTU 8N2, 8E1, 8O1, 8N1; 4.8 to 115.2 kbit/s; address 1 to 247 |
| Ethernet | 10/100Base-T; Modbus TCP, HTTP, FTP; www server, FTP server, DHCP client |
| Display | 4 x 4 1/2 LED digits, two-colour, 14 mm, backlit units |
| Dimensions and cut-out | 144 x 144 x 77 mm; cut-out 138 +0.5 x 138 +0.5 mm |
| Weight | 0.8 kg |
| Protection (EN 60529) | IP40 from the front, IP20 from the terminal side |
| Supply | 85 to 253 V a.c. (40 to 400 Hz) or 90 to 300 V d.c.; up to 12 VA |
| Ambient temperature | -10 to 23 to 55 degrees C, class K55 to EN 61557-12 |
| Humidity | 0 to 95%, no condensation; any operating position |
| Overload | Voltage 2 Un for 5 s; current 50 A for 1 s |
| Standards named | Immunity EN 61000-6-2, emission EN 61000-6-4, safety EN 61010-1; installation category III, pollution level 2 |
| Maximum phase-to-earth voltage | 300 V on supply and relays; 500 V on measuring input; 50 V on RS-485, Ethernet, pulse and analog circuits |
Choosing the N100 ordering code
The data sheet prints three codes. N100 11000M0 is 3 x 57.7/100 V with RS-485 only. N100 11100M0 is 3 x 57.7/100 V with Ethernet and an 8 GB memory. N100 21100M0 (this page) is 3 x 230/400 V with Ethernet and the 8 GB memory. All have 1 A / 5 A current inputs, one 0/4 to 20 mA output, three relays, one pulse input/output, an 85 to 253 V a.c. or 90 to 300 V d.c. supply, Polish and English documentation and a test certificate. A final digit of 2 (N100 21100M2) adds a paid calibration certificate. Pick 230/400 V for direct connection to a 400 V network and 57.7/100 V behind voltage transformers.
Installation and archive notes from the manual
Fit the N100 in a 138 x 138 mm opening with the four supplied screw clamps; terminals take wires up to 2.5 mm2. The pack includes an RS-485 connector. Supply, voltage inputs, current inputs, RS-485, Ethernet, pulse circuits, alarm outputs and analog outputs are galvanically separated. The manual describes the archive in the internal memory and copying it to an SD card, with its example of a 5-second archiving period filling an SD card in about three years. Keep a switch or circuit breaker near the meter, as the manual requires.
Typical uses in GCC plants
The N100 suits main low-voltage incomers, generator panels, desalination and water-pumping boards and industrial distribution panels where a PLC or SCADA reads Modbus TCP and an operator wants a large local display. The -10 to 55 degrees C rating applies to the air around the meter, so check hot enclosures.
Frequently asked questions
What does N100 21100M0 mean?
A 3-phase analyzer with 3 x 230/400 V voltage inputs, 1 A / 5 A current inputs, three relays, one analog output, Ethernet, RS-485 and an 8 GB memory.
Does the N100 have Ethernet?
Yes in this code, with Modbus TCP/IP, HTTP and FTP servers; N100 11000M0 is RS-485 only.
Up to which harmonic does it measure?
The feature list gives harmonics of voltage and current up to the 51st (the measuring table prints the 50th).
What is the panel cut-out?
138 x 138 mm for a 144 x 144 x 77 mm housing.
How many alarm relays are there?
Three programmable relay outputs, voltage-free NO contacts rated 250 V a.c. / 0.5 A a.c.
Documents and quotation
Need the N100 21100M0 for a project? Seven Star LLC, an independent supplier in Muscat, answers with a written quotation once we know the exact code and quantity. The Lumel N100 user manual is attached. Data sheet N100-19F supplies the three ordering codes and the technical tables used on this page. Please confirm ratings and approvals against current Lumel documents. Related range: Electrical & Power.
Datasheets & Documents
- Manual N100 power network analyzer user manual (Lumel) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Lumel is a Polish manufacturer of industrial measuring and automation devices based in Zielona Góra, known under this name since 1953. Its catalogue covers power network meters and analyzers, digital panel meters, controllers, recorders, transducers, current transformers and shunts.
Seven Star LLC is an independent supplier in Muscat. We list Lumel instruments, each with the manufacturer document, for switchboard builders and plant engineers in Oman and the GCC.
Lumel product series
Power measurement includes the N14 and ND20 three-phase power network meters with RS-485, the N43 DIN rail meter, the N100 network analyzer with Ethernet and the N32H digital DC circuit meter. The NF20 is a power factor controller for 4 to 12 capacitor steps.
Process instruments include the N31U universal digital panel meter, the RE82 PID temperature controller in 48 x 96 mm format, the RP3 three-phase thyristor power controller from 40 to 450 A and the HT20 Ethernet temperature and humidity monitor with PoE.
Where Lumel instruments are used
Switchboards and distribution panels, generator and capacitor bank panels, battery and rectifier circuits, industrial heating, plastics and food processing lines, and monitored storage and server rooms, wherever readings must reach a PLC, SCADA or building system.
Ordering Lumel instruments: what we need
Send the full ordering code, which defines inputs, supply voltage and communication, or give the measured quantities, CT and VT ratios, supply voltage, output and interface required.
Browse Lumel products by category: Power Meters & Power Quality.
Related products
Frequently Asked Questions
A 3-phase analyzer with 3 x 230/400 V voltage inputs, 1 A / 5 A current inputs, three relays, one analog output, Ethernet, RS-485 and an 8 GB memory.
Yes in this code, with Modbus TCP/IP, HTTP and FTP servers; N100 11000M0 is RS-485 only.
The feature list gives harmonics of voltage and current up to the 51st (the measuring table prints the 50th).
138 x 138 mm for a 144 x 144 x 77 mm housing.
Three programmable relay outputs, voltage-free NO contacts rated 250 V a.c. / 0.5 A a.c.