Sauter EGP100F412 Differential Pressure Transducer 0-300 Pa
Description
The EGP100F412 is a Sauter differential pressure transducer for gases with a 0 to 300 Pa (0 to 3.0 mbar) measuring range, a four-digit display and a run/fault LED. Its static capacitive sensor measures positive, negative and differential pressures, and it can be used for filter monitoring, room and duct pressure control or, with a flow probe, volume-flow measurement in ventilation systems.
Measuring pascals, not bars
Air-side pressures in ventilation are tiny: a few hundred pascals separate a clean filter from a clogged one and ten or twenty pascals decide whether a cleanroom or isolation room stays positive. The EGP100 is built for that regime. Two membranes record the pressure difference, a differential capacitive principle evaluates it, and the unit provides either a linear signal for pressure or a root-extracted signal that is proportional to volume flow or air speed across an orifice plate or flow probe.
Key features from the datasheet
- Static sensor with high accuracy for differential pressures below 1 Pa; also suitable for dusty air or air polluted with chemicals (not ATEX approved)
- Variable zero point and filter time constant (0.15 to 5.2 s) to suppress pressure surges
- Measuring range can be reduced to one third; linear or root-extracted characteristic
- 4-digit display shows actual value, unit and characteristic; status LED for run and fault
- Fits in any position, on a wall or on a DIN rail to EN 60715; cover opens without special tools
- Combinable with the XAFP100 flow probe for volume flow; manufacturer’s test certificate ex works
Technical specification
| Parameter | Specification |
|---|---|
| Type | EGP100F412 |
| Measuring range | 0 to 300 Pa (0 to 3.0 mbar) |
| Display / variable characteristic and LED | Yes / yes |
| Output signal | 0 to 10 V or 2 to 10 V (DIP switch or CASE Sensors software); load below 500 Ω switches automatically to 0 to 20 mA or 4 to 20 mA |
| Output limit | 10.6 V, so up to 6 % overrun of the range is transferred |
| Power supply | 24 V~/=, ±20 % |
| Power consumption | 3.0 VA at 24 V~; 1.3 W at 24 V= |
| Filter time constant | 0.15 to 5.2 s |
| Admissible positive pressure | ±20 kPa |
| Admissible operating pressure | ±7 kPa (recalibrate zero if exceeded) |
| Non-linearity | 1 % FS |
| Zero point stability | Below 0.3 % FS |
| Reproducibility | 0.2 % FS |
| Influence of position | Below 0.1 % FS (factory calibration for vertical fitting) |
| Media temperature | 0 to 70 °C |
| Ambient temperature / humidity | 0 to 60 °C / 5 to 95 % rh, no condensation |
| Pressure connection | Internal Ø 6 mm (6.2 mm tube) |
| Housing / cable gland | PC/ABS / M16 |
| Terminals | Screw terminals up to 1.5 mm² |
| Type of protection / class | IP65 (EN 60529) / III (EN 60730-1) |
| Weight | 0.19 kg |
Derived: the display shows up to 150 % of the set range with a linear characteristic, and up to 122 % with a root characteristic.
Selection and ordering guide
The EGP100 family has five measuring ranges and three equipment levels: F*01 basic, F*02 with variable characteristic and LED, F*12 with display, LED and variable characteristic. Symmetrical ranges support the linear characteristic only.
| Order code | Range | Display | Weight |
|---|---|---|---|
| EGP100F102 | ±75 Pa | No | 0.18 kg |
| EGP100F212 | ±150 Pa | Yes | 0.19 kg |
| EGP100F312 | 0 to 150 Pa | Yes | 0.19 kg |
| EGP100F412 | 0 to 300 Pa | Yes | 0.19 kg |
| EGP100F402 | 0 to 300 Pa | No | 0.18 kg |
| EGP100F612 | 0 to 1000 Pa | Yes | 0.19 kg |
Choose the range so that the normal working value sits comfortably within the lower to middle part of the scale. Output 0 to 10 V on the F*01 types; 0(2) to 10 V on F*02 and F*12.
Installation and wiring notes
- Any mounting position is allowed, but the unit is calibrated vertically, so allow for the position effect when fitting differently.
- Connect with 6 mm tubing; maximum measuring tube length is 15 m for a time constant under 0.5 s and 60 m for a time constant over 0.5 s.
- Use star wiring of the supply and do not connect inductive loads to the same transformer.
- Take the measuring-signal reference point MM from the device to the ground terminal of the analogue input.
- Zero point can be adjusted after fitting and must be re-done if the operating pressure is exceeded.
- LED: green normal; red sensor range exceeded by 40 % or fault; flashing red low voltage; orange indicates zero adjustment states.
Applications in Gulf building services and process rooms
Filter-bank monitoring on air-handling units is the volume use in the Gulf, where dust and sand load filters quickly and a differential-pressure reading shows when to change them. Differential pressure also controls laboratory, hospital and cleanroom pressure cascades and supports fan speed control through a frequency converter. The static sensor is explicitly rated for dusty air and chemically polluted air, but not for ATEX zones.
Selection and installation notes
A building automation device is selected from the signal type, the supply voltage, the mounting position and the system it connects to. Check the wiring diagram and the cable type, keep sensor cables away from power wiring, confirm the addressing or scaling in the controller, test each point at commissioning and record the final settings. Use the mounting accessories and the installation position given in the data sheet.
For differential pressure, connect the tubing to the correct ports, keep it short and free of kinks and set the zero at commissioning.
Information needed for a quotation
Send the full model code, the quantity, the delivery location in Oman or the GCC, the intended use and any accessories needed, so that the complete package can be quoted together.
Documents and supply information
The manufacturer data sheet is attached to this page and should be read together with the project specification and the site risk assessment before a purchase is confirmed. Ratings, standards and dimensions are quoted as printed on that sheet. Lead time, stock position and certificates available with the shipment are confirmed in the quotation, and we supply to Oman and the wider GCC region for industrial, utility and building services projects.
Accessories and related items
| Accessory | Description |
|---|---|
| 0010240300 | Connection set, 6 mm, complete |
| XAFP100F001 | Flow probe to measure the air volume in ventilation ducts |
| CERTIFICAT001 | Manufacturer’s test certificate type M |
| CERTIFICAT999 | Test for further device (from 2 pieces) |
| 0300360001 | USB-RS-485 converter |
Frequently asked questions
What range does the EGP100F412 measure?
0 to 300 Pa, which is 0 to 3.0 mbar, with a 4-digit display and status LED.
What is the output signal?
0 to 10 V or 2 to 10 V, selected by DIP switches or the CASE Sensors software; a load under 500 ohm changes the output to 0 to 20 mA or 4 to 20 mA automatically.
Can it measure volume flow?
Yes. With the root-extracted characteristic and a flow probe such as the XAFP100 or an orifice plate the signal becomes proportional to volume flow or air speed.
Is it suitable for hazardous areas?
The datasheet says it can be used for dusty or chemically polluted air but is not ATEX approved.
Who supplies the EGP100F412 in Oman?
Seven Star LLC is an independent supplier in Muscat and quotes against the exact order code. Confirm range, display and accessories before ordering.
Documents and quotation
The official Fr. Sauter AG product data sheet 32.021 for the EGP 100 (2021) is linked on this page. Send the order code and quantity to request a quotation. See more in Pressure Instrumentation.
Datasheets & Documents
- Datasheet Sauter EGP 100 product data sheet 32.021 (PDF, 2021) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
SAUTER is a Swiss building automation company based in Basel and active since 1910. The group designs and manufactures control valves, actuators, sensors, thermostats and room controllers for heating, ventilation and air conditioning in commercial, industrial and public buildings.
Seven Star LLC is an independent supplier in Muscat. We list SAUTER field devices against exact order codes and the official SAUTER data sheets, for HVAC contractors and facility teams in Oman and the GCC.
SAUTER product series
Valves and actuators include the VUG050F304 DN50 flanged control valve, the VKAI032F300 DN32 cut-off ball valve, the AKM115F120 rotary actuator for ball valves and the ASF112F222 spring-return damper actuator.
Sensors and controllers include the EGP100F412 differential pressure transducer, the EGQ222F032 CO2 and temperature room transducer, the EGT346F103 Ni1000 duct temperature sensor and the NRFC413MF111 Modbus fan coil thermostat. Safety devices include the TUC407F001 safety temperature limiter to EN 14597 and the DSF158F001 stainless pressure switch with SIL 2.
Where SAUTER products are used
Air handling units and fan coils, chilled and hot water circuits, boiler plants and room control in hotels, hospitals, offices, schools and laboratories connected to a building management system.
Ordering SAUTER products: what we need
Send the full SAUTER order code, such as VUG050F304. If unknown, give the valve size, Kvs and pressure rating, the actuator torque or force, control signal and supply voltage, and for sensors the range, output and mounting.
Browse SAUTER products by category: Valve Actuators.
Related products
Frequently Asked Questions
0 to 300 Pa, which is 0 to 3.0 mbar, with a 4-digit display and status LED.
0 to 10 V or 2 to 10 V, selected by DIP switches or the CASE Sensors software; a load under 500 ohm changes the output to 0 to 20 mA or 4 to 20 mA automatically.
Yes. With the root-extracted characteristic and a flow probe such as the XAFP100 or an orifice plate the signal becomes proportional to volume flow or air speed.
The datasheet says it can be used for dusty or chemically polluted air but is not ATEX approved.
Seven Star LLC is an independent supplier in Muscat and quotes against the exact order code. Confirm range, display and accessories before ordering.