- AC Drives
- Industrial Communications
- PLC & I/O Cards
- Vibration Monitoring
- Automation Accessories
- Controllers & Data Acquisition
- CCTV & Security
- Safety Switches & Guard Locking
- Encoders
- Industrial Computers
- HMI Displays
- Motor Soft Starters
- Isolator & Barrier
- Pneumatic Cylinders
- Servo Drives
- Automation Software
- Robotics
- Machine Vision
Brand: Circutor
Circutor LRZ 04-033 Line Reactor for Power Converters
Description
A 32 A, 0.98 mH line reactor for 15 kW drives
The Circutor LRZ 04-033 (code P73309) is a filter reactor for the network side of power converters. It has an inductance of 0.98 mH, a nominal current of 32 A and 45 W losses, and Circutor associates it with a 15 kW (20 CV) motor. LRZ is the low-power type, built with low-loss plates and wound with copper wire, with terminals for connection.
Frequency variators, UPS units and similar motor speed regulation equipment alter the network, affecting other loads. A reactor on the input can attenuate voltage peaks and reduce harmonic distortion; Circutor states that the LRZ and LRBZ reactors can reduce current harmonics in a converter from 40 to 50 percent to values around 20 percent, reduce short-circuit current and protect the converter semiconductors.
LRZ 04-033 functions
- 0.98 mH inductance, 32 A nominal current; 45 W losses
- Reduces converter current harmonics from 40 to 50 percent to about 20 percent (as stated by Circutor)
- Attenuates voltage peaks and micro-drops at connection and switching
- Can be installed on the network side or the motor side
- Reduces short-circuit current and improves semiconductor safety
- Copper wire winding; vacuum varnish sealing for insulation, mechanical strength and low noise
- Thermal class F (+155 C); class H (+180 C) on request
LRZ 04-033 technical specifications
Electrical
| Parameter | Specification |
|---|---|
| Allowable / permanent overload | 1.7 In / 1.7 In |
| Maximum transient current | 2 In for 1 minute |
| Linearity (5 percent L) | 1.5 In |
| Insulation voltage, circuit | 4 kV |
| Voltage level | Up to 1000 V ac |
| Motor power | 15 kW / 20 CV |
| Losses | 45 W |
| Nominal current In | 32 A (other values on request) |
| Inductance L | 0.98 mH |
| Type and code | P73309. / LRZ 04-033, reactor |
Mechanical, thermal and standards
| Parameter | Specification |
|---|---|
| Applicable standards | UNE-EN 60289, IEC 60076 |
| Ingress class | IP 00 |
| Thermal class | Class F (+155 C); on request class H (+180 C) |
| Conductor | Copper wire |
| Mass | 4.3 kg |
| Size (W x H x D) | 150 x 152 x 90 mm |
LRZ / LRBZ range, network side, 50 Hz (codes as printed)
| Code | Type |
|---|---|
| P7330M. | LRBZ 04-300 |
| P7330K. | LRBZ 04-200 |
| P7330J. | LRBZ 04-185 |
| P7330G. | LRBZ 04-115 |
| P7330E. | LRBZ 04-080 |
| P7330B. | LRZ 04-050 |
| P73309. | LRZ 04-033 |
Matching the reactor to the drive
The type number follows the current: the LRZ 04-033 is for a 32 A drive input, roughly a 15 kW motor, according to the datasheet table. For drives above that the range continues with LRZ 04-050 and the LRBZ reactors with copper strip coils. Select by the drive input current and a margin: the reactor tolerates 1.7 In continuously and 2 In for one minute, with linearity up to 1.5 In. If the application needs a different current or impedance, Circutor states other values are available on request.
Installation notes
The reactor is an open construction (IP 00) of 150 x 152 x 90 mm and 4.3 kg, so mount it inside a drive cabinet or enclosure with adequate ventilation, and connect it with suitable terminals. Fit it between the supply and the converter input; installing on the motor side also attenuates switching harmonics. Heat dissipation of 45 W should be included in the cabinet thermal calculation, and the Class F rating (+155 C) is the insulation limit, not the ambient limit.
Where the LRZ 04-033 is used
Common on variable-speed drive panels for pumps, fans and compressors of about 15 kW, and on UPS inputs. For plants with weak supplies or generator sets, line reactors reduce stress on the converters, though the final choice between reactors, active filters or both depends on the harmonic study.
Selection and installation notes
A line reactor is chosen from the drive power and the rated current of the converter, so check both against the sheet and allow for the ambient temperature inside the cabinet. Mount it where air can circulate around the windings, keep the connecting cables short and tightened to the torque in the instructions, and remember that the losses listed on the sheet become heat in the panel. Where harmonic limits apply to the site, confirm the final choice with a measurement or with the drive manufacturer recommendation.
Information needed for a quotation
Send the full model code, the quantity, the delivery location in Oman or the GCC, the intended use and any accessories needed, so that the complete package can be quoted together.
Documents and supply information
The manufacturer data sheet is attached to this page and should be read together with the project specification and the site risk assessment before a purchase is confirmed. Ratings, standards and dimensions are quoted as printed on that sheet. Lead time, stock position and certificates available with the shipment are confirmed in the quotation, and we supply to Oman and the wider GCC region for industrial, utility and building services projects.
Related Circutor items
The LRBZ 04-080 (P7330E) is the higher-current copper strip type on this site. For stronger harmonic mitigation see the AFQs-3WF-030M active filter, and the computer SMART III regulators for capacitor banks.
Frequently asked questions
What is the LRZ 04-033 rated for?
32 A nominal current, 0.98 mH inductance, for a 15 kW (20 CV) motor drive.
Can it be used on the motor side?
Yes. Circutor states the LR series can be used on the network side and the motor side.
How much can it reduce harmonics?
Circutor states current harmonics can fall from 40 to 50 percent to values around 20 percent.
What thermal class does it have?
Class F (+155 C), with class H (+180 C) on request.
Is Seven Star LLC a distributor of Circutor?
No. Seven Star LLC is not a Circutor distributor; it is an independent Muscat supplier that obtains genuine Circutor products against customer enquiries.
Documents and quotation
This listing carries the LRZ 04-033 datasheet (generated 21/10/2026) for reference. Use it with the manual to confirm the correct order code, then send the code, options and quantity via the quote form. Seven Star LLC works from Muscat as an independent supplier for GCC customers, and prices are provided on request only. Always confirm ratings, options and approvals against the latest manufacturer documents. See Electrical & Power and the Circutor brand page for related items.
Datasheets & Documents
- Datasheet Circutor LRZ 04-033 datasheet (generated 21/10/2026) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Circutor is a Spanish manufacturer of equipment for power factor correction, harmonic filtering and electrical measurement, founded in 1973 and based in Viladecavalls near Barcelona.
Seven Star LLC is an independent supplier in Muscat. We list Circutor power quality equipment, each with the manufacturer datasheet, for industrial plants, commercial buildings and utilities in Oman and the GCC.
Circutor product series
Power factor controllers include the computer SMART III 14, the SMART III Fast 6 for static (thyristor) capacitor banks, the SMART III F6-12Vdc and the computer C6 with Wi-Fi. The OPTIM SVGm-200-440 and SVGm-600-440 are hybrid var compensators that combine capacitor steps with an active generator for fast, stepless correction.
The AFQs-3WF-030M is a 30 A active harmonic filter, the LRZ 04-033 and LRBZ 04-080 are line reactors for power converters, and the CIRWATT B410T is an energy meter for tariff and sub-metering points.
Where Circutor equipment is used
Industrial plants, commercial buildings and utilities with large motor, drive or air-conditioning loads, to hold power factor, limit harmonic distortion, protect converters and measure energy.
Ordering Circutor equipment: what we need
Send the product code, system voltage and frequency, the current transformer ratio, the number of capacitor steps or the load in kvar or amps, and the quantity.
Browse Circutor products by category: Power Meters & Power Quality.
Related products
Frequently Asked Questions
32 A nominal current, 0.98 mH inductance, for a 15 kW (20 CV) motor drive.
Yes. Circutor states the LR series can be used on the network side and the motor side.
Circutor states current harmonics can fall from 40 to 50 percent to values around 20 percent.
Class F (+155 C), with class H (+180 C) on request.
No. Seven Star LLC is not a Circutor distributor; it is an independent Muscat supplier that obtains genuine Circutor products against customer enquiries.

Reviews
There are no reviews yet.