Allen-Bradley 1734-OE4C POINT I/O 4-Channel Analog Current Output Module

Description

Four 4-20 mA outputs in one POINT I/O slot

The Allen-Bradley 1734-OE4C provides four analog current outputs for valve positioners, drive speed references and other 4 to 20 mA or 0 to 20 mA loads. Each channel is single-ended and non-isolated, and the output stays at 0 mA until communication with the controller has been established.

It is the high-density counterpart of the two-channel 1734-OE2C. Choose it where more outputs are needed per node and the larger field supply current (220 mA) is available.

Technical specifications

Parameter Specification
Manufacturer / family Allen-Bradley (Rockwell Automation) / POINT I/O
Catalog number 1734-OE4C (1734-OE4CK is the coated version)
Outputs 4 analog, single-ended, non-isolated
Output current range 4 to 20 mA or 0 to 20 mA, user configurable
Resolution 16 bits over 0 to 21 mA, 0.32 uA per count
Absolute accuracy, min 0.4% (0.1% if calibrated)
Accuracy drift with temperature Less than 50 ppm per C
Resistive load on mA output 0 to 750 ohm
Conversion rate / step response 1 us / 160 us max. to 63% of value
Surge current 2 A for 10 ms, repeatable every 3 s
Field power input 10 to 28.8V DC including 5% AC ripple, 220 mA, Class 2
External supply current, nominal 110 mA at 24V DC including outputs at 20 mA
Power dissipation, max 1.86 W at 750 ohm on each output; 2.15 W at 0 ohm
Dimensions (H x W x D) / weight 56.6 x 12.1 x 77.5 mm / 36.9 g
Keyswitch position 4

Accuracy, load and response

The sheet lists a resolution of 16 bits over 0 to 21 mA (0.32 microamps per count). Absolute accuracy at the current terminal is at least 0.4%, improving to 0.1% when the channel is calibrated, with a temperature drift below 50 ppm per C. The two-channel module is specified at 0.1% without calibration, so the difference should be checked against the loop requirement.

The output drives 0 to 750 ohm loads, converts in 1 microsecond and reaches 63% of a step in 160 microseconds at most. A surge current of 2 A for 10 ms, repeatable every 3 seconds, is permitted. Power dissipation reaches 2.15 W with shorted (0 ohm) outputs, so allow for the heat when many modules sit together.

Installing and powering the module

Field power is 10 to 28.8V DC including 5% AC ripple, at 220 mA maximum and 110 mA nominal at 24V DC with each output at 20 mA. POINTBus supplies 75 mA. The module fits 1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS and the 3-wire bases, with the keyswitch at position 4.

Wire with shielded copper, 23 to 13 AWG at 100 °C or higher, wire category 2 on signal and 1 on power ports. There is no isolation between outputs or between outputs and field power. The status indicators show network, module and one output state per channel. Remember to keep output wiring away from power cables, and follow the shield-grounding guidance of the wiring and grounding guidelines, publication 1770-4.1.

Documents and quotation

The sheet 1734-IN034 contains the output table and the certification page. Provide the 1734-OE4C reference, quantity, the controller or adapter and the loads on each channel when you request a quotation. Related parts are listed in PLC & I/O Cards.

How the 1734-OE4C Works

The controller writes a value for each channel to the 1734-OE4C through the network adapter and POINTBus. The module’s digital-to-analog converter turns that value into a current that the output stage drives through the field loop, from the module terminal, through the load, and back to the field power common. Because the output is a regulated current source, the signal stays correct regardless of cable resistance, as long as the total loop resistance stays within the 0–750 Ω limit. This is why current outputs are preferred for long runs to valve positioners and drives out in the plant.

In the 4–20 mA range the live zero lets the receiving device detect a broken wire, since it would see 0 mA instead of at least 4 mA. The module also holds its outputs at 0 mA until the controller connection is established, so field devices start from a defined state at power-up.

Selection & Ordering Guide for the 1734-OE4C

  • 1734-OE4C – four current outputs, 0–20 mA or 4–20 mA.
  • 1734-OE4CK – conformal-coated version.
  • 1734-OE2C – two current outputs, with higher uncalibrated accuracy.
  • 1734-OE2V – two voltage outputs, 0–10 V or ±10 V, for devices with voltage inputs.

Each module needs a POINT I/O terminal base with the keyswitch at position 4 and an adapter at the head of the node. Check the input resistance of every receiving device and add the cable resistance to confirm the loop stays within 750 Ω. Our team can help confirm the correct ordering code when you request a quote.

Installation & Maintenance of the 1734-OE4C

  • Size the field power supply for the 220 mA maximum draw of each module, in addition to any other modules on the same field power bus.
  • Since the outputs are not isolated from each other, use a signal isolator for any receiving device whose input is referenced to a different earth.
  • POINT I/O supports removal and insertion under power, but only when the area is known to be non-hazardous.
  • Where the application needs the tighter 0.1% figure, calibrate the channels as described in the Rockwell documentation and record the results.
  • At commissioning, measure each loop with a calibrated meter at 4, 12 and 20 mA and check that the actuator moves to the matching position.

Typical Applications in Oman & the GCC

The 1734-OE4C commonly drives control valve positioners on water transmission and desalination plants, speed references to variable-frequency drives on pumps and cooling-tower fans, damper actuators in HVAC and district cooling systems, and set-points for burner and dosing controls in process skids. Four outputs in one 12 mm slot allow a compact remote I/O panel close to the process, with only a network cable back to the control room.

Why Source from Seven Star LLC

Seven Star LLC is an independent supplier in Muscat. Seven Star LLC supplies Allen-Bradley POINT I/O and other automation components across Oman and the GCC. Send the 1734-OE4C catalog number, the quantity and the loads on each channel and request a quote; our team can help confirm the correct ordering code, terminal base and adapter.

Datasheets & Documents
  • PDF Installation Instructions Allen-Bradley POINT I/O 1734-OE4C 4-Channel Analog Current Output Module Installation Instructions (1734-IN034) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Catalog numbers beginning 1756, 1734, 1746 or 5069 are read at a glance by anyone who maintains Allen-Bradley control panels. The brand, the control hardware name of Rockwell Automation, dates back to 1903 in Milwaukee, USA. Seven Star LLC sources and supplies Allen-Bradley PLC and I/O modules, communication adapters and PowerFlex drives for plants in Oman, matching catalog number, series letter and firmware against the manufacturer's documentation.

Allen-Bradley product families listed here

Current controller platforms on this page are ControlLogix, with the 1756-L85E ControlLogix 5580 controller and the 1756-PA72 chassis power supply, and CompactLogix 5380, with the 5069-L320ER and 5069-L340ERM. Distributed I/O is represented by POINT I/O: the 1734-AENTR dual-port EtherNet/IP adapter and the 1734-IB8 digital input module. Allen-Bradley drives listed include the PowerFlex 525 and PowerFlex 755. For installed systems there are SLC 500 parts: the 1746-A10 chassis, 1746-NI16I analog input module, 1747-ASB remote I/O adapter, 1747-KE interface and 1747-M13 memory module.

Where Allen-Bradley hardware is used

ControlLogix and CompactLogix controllers run packaged equipment and plant utilities: compressor and pump skids, water and wastewater plants, power distribution, material handling and packaging lines. PowerFlex drives control pumps, fans and conveyors. Many SLC 500 racks are still in service.

Ordering Allen-Bradley modules and drives: what we need

Send the full catalog number, the series letter and, for controllers and communication modules, the firmware revision printed on the side label. Compatibility with an existing project depends on these. For PowerFlex drives, give the complete catalog string, which encodes voltage, current rating, enclosure and options, plus the motor nameplate data. For SLC 500 parts, tell us the rack size and processor so that we can check slot and power supply loading in the manufacturer's manuals. A label photo avoids most mistakes.

Frequently Asked Questions

How many outputs does 1734-OE4C have?
Four analog current outputs, single-ended and non-isolated.
What is the accuracy?
At least 0.4% at the current terminal, or 0.1% if calibrated, with a drift below 50 ppm per C.
How large a load can it drive?
The sheet lists a resistive load of 0 to 750 ohm on the mA output.
How does it differ from 1734-OE2C?
The OE4C has four channels and a 220 mA field supply requirement; the OE2C has two channels and a 70 mA supply current.
Which keyswitch position applies?
Position 4.