Brand:

ABB ACH580-01-145A-4 HVAC AC Drive 75 kW 145 A

Description

Where the ACH580-01-145A-4 fits in a building

ACH580-01-145A-4 is a wall-mounted ABB ACH580 drive made for heating, ventilation and air conditioning. ABB’s catalogue rates it at 75 kW and 145 A in no-overload use on a 380 to 415 V network, and builds it on frame R6. Typical jobs are supply and extract fans, chilled-water and heating pumps, cooling-tower fans and similar variable-torque loads in commercial and industrial buildings. It is the only 75 kW rating and sole occupant of frame R6 in this table.

Among the HVAC features in the control program are real-time clock scheduling, PID controllers for process control, motor flying start and motor preheating. Related products are in AC drives and on the ABB ACS580 page.

Technical specifications

Parameter Specification
Type designation ACH580-01-145A-4
Platform ACH580-01 wall-mounted HVAC drive
Input supply Code 4: 380-415 V or 440-480 V, three-phase
Housing frame R6
No-overload rating (400 V) 75 kW, 145 A
Light duty (400 V) 138 A, 75 kW
Light duty (480 V) 124 A, 100 hp
Enclosure options IP21 standard; +B056 gives IP55
Size in IP21 727 mm with gland box (548 mm without) x 252 x 369 mm
IP21 net weight 42.4 kg
Size and weight in IP55 727 x 252 x 380 mm, 43 kg
Next sizes in table Below: ACH580-01-106A-4 (55 kW); above: ACH580-01-169A-4 (90 kW)

Reading the 145 A rating

Start from 138 A: this is the continuous light-duty current at 400 V, enough for a 75 kW fan or pump motor, with 110% for one minute (about 151.8 A, derived). If the motor is wound for 460 V or 480 V, read the 124 A, 100 hp column instead. The nominal 145 A figure is for loads without any overload demand.

Frame R6 in IP21 form stands 727 mm tall including the gland box (548 mm without it), 252 mm wide and 369 mm deep, and weighs 42.4 kg. The IP55 build measures 727 x 252 x 380 mm at 43 kg. The catalogue lists no switch or C1 variant for frames above R5.

ABB’s selection guide for IE4 synchronous reluctance motors names the ACH580-01-145A-4 as the matched drive for 55 kW M3BL225SMF4 at 3000 rpm (122 A nominal, motor efficiency 95.3%, package efficiency 92.6%); 55 kW M3BL250SMA4 at 1500 rpm (121 A nominal, motor efficiency 95.7%, package efficiency 93.1%). Package values are calculated for the drive and motor together, so treat the table as a selection aid rather than a commitment for other motors.

Options that change the order

An order line starts with ACH580-01-145A-4: 01 marks the wall-mounted drive, 145A is the rating field and 4 the voltage class. Typical plus codes are +L512 for CHDI-01 with 115/230 V inputs, +B056 for IP55, +F278 for a main disconnect switch with auxiliary contact and +F316 for the disconnect switch plus a C1 filter.

Add a fieldbus only when the building network needs one: PROFINET IO via FPNO-21 (+K492), EtherNet/IP via FEIP-21 (+K490) and PROFIBUS DP via FPBA-01 (+K454) are among the choices.

On board you get six digital inputs and two analog inputs, two analog outputs and three relay outputs, a 24 V DC auxiliary supply of 250 mA, thermistor inputs for PTC and Pt100, Pt1000, KTY or Ni1000 sensors and an operating range of -15 to +50 degrees C.

Source document and RFQ

Request the ACH580-01-145A-4 from Seven Star LLC with your motor nameplate, supply voltage and communication needs; the quotation gives availability and lead time. Ratings, dimensions, motor pairing and option codes on this page were taken from ABB catalogue 3AUA0000186691, revision F (9.14.2019), available via the document link.

Confirm before ordering: type code and plus options, motor rated current, enclosure class, ambient temperature and altitude, and any change in newer ABB documents.

Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

ABB, formed in 1988 and headquartered in Zurich, covers an unusually long stretch of a plant's equipment list, from the flowmeter and analyzer in the field to the drive, breaker and protection relay in the electrical room.

Seven Star LLC is an independent supplier serving Oman and the GCC. Our ABB listing concentrates on measurement and analytics: ABB flowmeters, liquid analysis sensors and systems, level and pressure instruments. It also includes valve actuators, low voltage circuit breakers, ABB drives, soft starters and protection relays.

ABB product families on this page

Flow measurement includes ABB electromagnetic, Coriolis, vortex and swirl meters, sold under names such as ProcessMaster, AquaMaster, CoriolisMaster and SwirlMaster. Liquid analysis covers pH, conductivity and dissolved oxygen sensors with their transmitters. SensyTemp TSP sensors handle temperature. On the electrical side the listing has ACS355 machinery drives, the ACS550 general purpose drive, the ACQ580 for water and wastewater and the ACS880-01 industrial drive, with fieldbus adapters such as the FPBA-01 for PROFIBUS DP. Protection and switching products include SACE Tmax XT molded case breakers, SACE Emax 2 air circuit breakers, PSR soft starters and the REM615 and RET615 relays.

Where ABB instruments and drives are used

Water and wastewater plants use the electromagnetic flowmeters, analyzers and ACQ580 drives together. Oil and gas, power and chemical plants specify the Coriolis and vortex meters, pressure and level transmitters and the 615 series relays for motor and transformer feeders. The drives run pumps, fans, conveyors and compressors in almost every industry.

Ordering ABB parts: what we need

For drives send the full type code from the rating label, for example ACS355-03E-05A6-4, plus the serial number if it is a replacement. For instruments send the complete order code, measuring span, process connection, wetted materials, output or protocol and the hazardous area approval. For breakers give frame size, rated current, breaking capacity, number of poles, trip unit and fixed or withdrawable version.

Frequently Asked Questions

What are the light-duty ratings of the ACH580-01-145A-4?
ABB lists 138 A for 75 kW on a 380 to 415 V network and 124 A for 100 hp on a 440 to 480 V network, with a nominal rating of 145 A.
Which frame size and weight does the ACH580-01-145A-4 have?
It is frame R6. In IP21 it weighs 42.4 kg and measures 252 x 369 mm in width and depth; the IP55 version weighs 43 kg.
How is the IP55 version of the ACH580-01-145A-4 ordered?
Add the plus code +B056 to the type designation. The catalogue calls it the IP55 unit for wall-mountable drives and lists 727 x 252 x 380 mm for frame R6.
Which building-automation protocols are built into the ACH580-01-145A-4?
BACnet MS/TP, Modbus RTU and N2 are included as standard. BACnet/IP and other networks need an F-series adapter, for example FBIP-21 with +K465.
Which motor does ABB pair with the ACH580-01-145A-4?
The catalogue lists ACH580-01-145A-4 as matched drive for 55 kW M3BL225SMF4 at 3000 rpm; 55 kW M3BL250SMA4 at 1500 rpm.