The DKG-309 is a comprehensive automatic mains failure (AMF) unit for single-genset standby or dual-genset mutual standby operation. It comes in two versions: MPU, which uses a magnetic pickup for speed, and CANBUS, which connects to ECU-controlled electronic engines over J1939 so that engine control, protection and instrumentation need no extra senders and ECU warnings are displayed in text. The DKG-309 is a straightforward panel-mount unit with plug-in connectors, and every program parameter can be changed from the front pushbuttons without an external programming unit. It is listed with other items from our diesel generator spare parts category.

Technical specifications

Parameter Specification
Model DKG-309 (CANBUS and MPU versions)
Alternator voltage 0 to 300 V-AC (Ph-N)
Alternator frequency 0-100 Hz
Mains voltage / frequency 0 to 300 V-AC (Ph-N) / 0-100 Hz
V, A, cos accuracy 1.0% + 1 digit
kW, kVA, kVAr accuracy 2.0% + 1 digit
DC supply range 9.0 to 33.0 V-DC
Typical standby current 100 mA-DC
Maximum operating current 200 mA-DC (relay outputs open)
Cranking dropouts Survives 0 V for 100 ms
Generator / mains contactor relay outputs 16 A at 250 V
DC outputs 1 A at 28 V protected semiconductor output
Charge excitation Min. 2 W
Magnetic pickup input 0.5-30 V-AC, 10 kHz max.
Current inputs From CTs, …/5A; max. load 0.7 VA per phase
Analog input range 0-5000 ohms
Inputs and outputs 4 configurable analog inputs, 7 configurable digital inputs, 2 configurable and 6 total digital outputs
Serial port RS-232, 9600 baud, no parity, 1 stop bit
Operating temperature -20 C to 70 C
Storage temperature -40 C to 80 C
Maximum humidity 95% non-condensing
Dimensions (W x H x D) 172 x 134 x 46 mm
Panel cut-out 151 x 111 mm minimum
Weight Approx. 340 g
Case material High-temperature ABS/PC (UL94-V0)
Protection degree IP65 front panel, IP30 rear
Installation Flat surface on a Type 1 enclosure, rear plastic brackets

Conformity entries on the datasheet: EN 61010 (safety) and EN 61326 (EMC) as CE reference standards, and UL/CSA certificate 20110527-E314374 referencing UL 508 Edition 17, UL 2200 1st Edition, UL 840 Edition 3 and CSA C22.2 No. 14 Edition 10.

Operating modes, alarms and telemetry

The user manual describes five modes. STOP energises the mains contactor if the mains phase voltages are within limits and keeps the engine stopped. AUTO is the genset and mains automatic transfer mode: when any mains phase leaves its limits the mains contactor drops, the engine starts after the preheat timer, runs unloaded for the heating period and then closes the generator contactor once voltage and frequency are in limits. On mains return the engine keeps running for the mains waiting period, load goes back to mains, and the unit applies the cooldown before stopping the fuel solenoid. RUN keeps the set running in an emergency backup mode, and TEST transfers the load to the genset indefinitely.

Faults are divided into three priority levels: alarms (immediate genset contactor release and engine stop), load dumps (contactor release and stop after cooldown) and warnings. The manual lists protections for low oil pressure, high temperature, low fuel, low coolant level, rectifier fail, emergency stop, low and high speed, start fail, stop fail, overload, excess power, low and high genset voltage, battery voltage, charge failure, mains phase-order fail and ECU fail. The last 100 events are logged with time stamps and 18 measured parameters, and the RS-232 port supports Rainbow remote monitoring, MODBUS, and GSM or PSTN modems with SMS sending on fault.

Selection and installation notes

Order the MPU version for mechanical-governor engines that provide a magnetic pickup, and the CANBUS version for J1939 electronic engines; state the engine make and model when you request a quote. The unit accepts selectable oil-pressure sender types such as VDO 0-7 and 0-10 bar and DATCON ranges, and a programmable table for non-standard senders. Mount the unit in a 151 x 111 mm cut-out, connect a fused DC supply of 9-33 V-DC, and make sure the battery negative is grounded as shown in the typical connection drawing. Mutual standby needs two units and the I/O expansion port can add relay expansion modules (up to 22 relays, 16 volt-free, with two modules).

Other programmable features listed in the datasheet include a built-in daily, weekly and monthly exerciser, weekly operation schedule programs, multiple language support, a customer logo display capability, event logging with time stamp and measurements, and I/O expansion. The battery-backed real time clock keeps the schedule and the event times correct after a supply loss, and the plug-in connection system allows a replacement unit to be fitted without rewiring.

Selection and installation notes

A generator controller is selected from the start and transfer logic needed, the number of sets, the engine and alternator signals and the communication required. Check the battery supply range, wire the voltage and current inputs and the engine sensors as the manual shows, set the engine and protection parameters from the engine and alternator data and test the start, stop, transfer and every protection with the set running before handover. Keep a copy of the parameter file with the site documents.

Information needed for a quotation

Send the full model code, the quantity, the delivery location in Oman or the GCC, the intended use and any accessories needed, so that the complete package can be quoted together.

Documents and supply information

The manufacturer data sheet is attached to this page and should be read together with the project specification and the site risk assessment before a purchase is confirmed. Ratings, standards and dimensions are quoted as printed on that sheet. Lead time, stock position and certificates available with the shipment are confirmed in the quotation, and we supply to Oman and the wider GCC region for industrial, utility and building services projects.

Documents and quotation

Both the datasheet and the user manual (63 pages, version dated 23.08.2013) from Datakom are provided for download. Contact us with the engine model and version needed for a quotation.

Datasheets & Documents
  • PDF Datasheet DKG-309 datasheet (Datakom) Download
  • PDF User manual DKG-309 user manual V-29 (Datakom) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Datakom is a Turkish manufacturer of generator controllers and power measurement electronics, headquartered in Ümraniye, Istanbul. It was founded in 1988 as a three-person electronic design house, began manufacturing in 1990 and launched its own genset control products in 1994. Datakom now offers more than 400 products, including the Rainbow SCADA remote monitoring software.

Seven Star LLC is an independent supplier in Muscat. We list Datakom products with the manufacturer datasheets and manuals, for generator packagers and maintenance teams in Oman and the GCC.

Datakom company profile

Founded 1988, Istanbul, Turkey
Headquarters Ümraniye, Istanbul
Own products Genset controllers, from 1994
Range More than 400 products
Product families D-300 and D-500 MK3 genset controllers, DKG automatic mains failure and transfer switch controllers, AVR alternator voltage regulators, DKM network analysers, DFC reactive power controllers, Rainbow SCADA software

Milestones

  • 1988: Datakom is founded as a design house.
  • 1990: Manufacturing begins.
  • 1994: Datakom launches its own genset controllers.

Datakom product series

Genset controllers on this site include the D-300 MK3 and the advanced D-500 MK3, which support J1939 CANBUS engines, as well as the DKG-309 automatic mains failure unit and the DKG-171 transfer switch controller. The DKG-605 is an alarm annunciator.

Companion products include the AVR-8 alternator voltage regulator, the SBC-245 24 V 5 A smart battery charger, the DKM-409 network analyser with scopemeter function, the DPR-350 network analyser and protection relay and the DFC-0124 reactive power controller for capacitor banks.

Where Datakom products are used

Stand-by and prime power gensets for oil and gas camps, utilities, telecom sites, hospitals and commercial buildings, changeover panels, capacitor banks and energy monitoring in low-voltage switchboards.

Datakom products we list

Family Examples
Diesel Generator Spare Parts AVR-8 Alternator Voltage Regulator, D-300 MK3 Genset Controller, D-500 MK3 Advanced Genset Controller, DKG-171 Automatic Transfer Switch Contro…, DKG-309 Automatic Mains Failure Unit
Controllers & Data Acquisition DFC-0124 Reactive Power Controller, DKM-409 Network Analyser with Scopemeter

Ordering Datakom products: what we need

Send the model and variant, the engine make and ECU or magnetic pickup, the alternator, the number of phases and voltage, and the communication options needed. For replacements, send a photo of the label on the installed unit.

Facts checked against Datakom's own company profile (datakom.com.tr), October 2026.

Frequently Asked Questions

What is the difference between the MPU and CANBUS versions?
The CANBUS version connects to ECU-controlled electronic engines over J1939 and shows ECU alarms as text; the MPU version uses a magnetic pickup input.
Can it run two gensets in mutual standby?
Yes, the datasheet lists dual genset mutual standby operation.
How many events does it store?
The last 100 events with date-time stamps and 18 measured parameters.
What is the DC supply range?
9.0 to 33.0 V-DC, with ride-through of 0 V cranking dropouts for 100 ms.
Which communication options exist?
An RS-232 port with Rainbow PC software, MODBUS, and GSM or PSTN modem support including SMS on fault.