Brand:

ABB ACS880-01-061A-3 ACS880-01 30 kW Frame R4 AC Drive

Description

ABB ACS880-01-061A-3 frame R4 drive at 380 to 415 V

Within the ACS880-01 series, ABB ACS880-01-061A-3 covers the 61 A step. It is packaged in frame R4, intended for wall mounting, and designed for 380 to 415 V three-phase networks.

A Bluetooth-capable ACS-AP-W assistant panel is included, and the standard type carries no EMC filter, so a filter plus code is needed where C2 or C3 emission limits apply.

Technical specifications

Parameter Specification
Type code ABB ACS880-01-061A-3
Series ACS880-01 wall-mounted single drive
Frame size R4
Supply voltage 3-phase 380 to 415 V, +10% / -15%, 50/60 Hz
Nominal output current 61 A
Nominal motor power (400 V) 30 kW
Light / heavy duty (400 V) 58 A / 30 kW and 45 A / 22 kW
Maximum output current 76 A
Input current (400 V) 61 A
Standard IP21 enclosure 203 x 580 x 274 mm, 18.6 kg
IP55 option +B056 203 x 735 x 344 mm, 19.1 kg
Typical loss / air / noise 818 W, 280 m3/h, 64 dB(A)
gG fuse 80 A, OFAF000H80
aR fuse option 100 A, 170M1567
UL class T fuse JJS-80
Copper cable 3×25 mm2 (UL 4)
Motor cable, maximum 300 m
Output frequency 0 to 598 Hz
Operating temperature -15 to +55 C with derating; up to 4000 m
Safety and panel Safe torque off, ACS-AP-W panel, coated boards, DC choke

Fitting frame R4: space, air and fuses

Plan a footprint of 203 x 580 mm with 274 mm depth and a mass of 18.6 kg. The manual asks for 200 mm clear above and 300 mm below, and quotes 818 W typical loss with 280 m3/h of air and 64 dB(A).

For the input circuit ABB lists a 80 A gG fuse (type OFAF000H80, size 000) with a minimum short-circuit current of 800 A. An ultrarapid alternative is Bussmann 170M1567 at 100 A, and the UL class T choice is JJS-80. A brake chopper is built into this frame as standard, so a brake resistor can be connected directly.

Frame R4 allows a maximum recommended motor cable length of 300 m. Longer cables or higher switching frequencies may stop the EMC Directive requirements from being met, according to the hardware manual.

Start from the motor nameplate current rather than the kilowatt figure alone. At 400 V this drive supplies 61 A nominal (30 kW), 58 A light duty or 45 A heavy duty, with 76 A as the maximum output current.

Because the code ends in -3, ratings are given for a 400 V supply alone; a higher-voltage network needs a -5 drive.

Reading the ACS880-01-061A-3 order code

Options are written as plus codes after the type. ABB lists +B056 (IP55), +C135 (flange mounting), +C132 (marine type approval), +D150 (brake chopper), +E200/+E201/+E202 (EMC filters) and +N5700 among others; not every code exists for every size.

For a project with several ACS880-01 sizes, list each drive code with its frame, motor power and cabling next to the others in one schedule. That makes it easier to check cabinet space, cooling air and fuse selection together, and to see whether the ACS880-01-061A-3 can share accessories with neighbouring ratings.

Application checks for a 30 kW ACS880-01

The 61 A rating of this drive covers many 30 kW pumps, fans and compressors on a 400 V network, but the application decides which current column applies. Ask how the load behaves at start, how often it starts and stops, and whether it ever has to hold torque at low speed. A water transfer pump running at steady speed is a very different duty from a crusher feeder or a hoist that sees repeated overload. When the heavy-duty figure is the relevant one, compare it honestly with the motor nameplate current; if it falls short, move to the next size up rather than relying on the maximum current for continuous work.

Where the motor must stop quickly or is driven by the load, plan the brake resistor at the design stage and confirm its rating with the ABB documentation. Also decide early which control signals and safety functions the project needs, because these affect the option list.

Cooling the drive in Gulf plant rooms

With 818 W of typical losses, this drive adds a meaningful heat load to a motor control room. In Oman and neighbouring GCC countries, where outside air in summer can be close to the drive operating limit, the room cooling design should include the losses of every drive installed there, not only this one. Avoid placing the drive where it draws in warm air from another unit, and keep the free space above and below clear so that the airflow stated by ABB can actually pass through the heatsink.

For pump stations or desalination and water facilities with dusty or salty air, review the enclosure choice carefully. The IP55 option listed on this page, or a filtered and cooled cabinet, can help keep dust and moisture away from the electronics, while condensation should be prevented by keeping the room conditioned even when the drive is stopped.

Start-up procedure

Check the incoming supply voltage against the -3 rating before energising, confirm that fuses match the types listed in the protection data, and verify that the motor and supply cable screens are terminated as the hardware manual describes. Enter the motor data, choose the control mode suitable for the load, run the motor identification and then test the start, stop and speed reference signals from the control system. Prove the Safe torque off function before handing over the machine.

Keeping the drive in service

Schedule regular cleaning of the air path, check that the cooling airflow is not reduced, inspect cable terminations for signs of overheating, and back up the parameters after any change. Keep the type code and option list in the maintenance file so a matching unit can be identified quickly if a replacement is ever required.

Documents and quotation

Where this page quotes ratings, fuses and losses, the origin is ABB’s ACS880-01 hardware manual; the catalogue adds ordering context. Browse AC Drives or see the ACS880-01 family.

Please match the exact type code and options to the installed equipment first. Seven Star LLC supplies as an independent business in Muscat and gives availability with each quotation.

Datasheets & Documents
  • PDF Catalog ABB ACS880 single drives catalog (3AUA0000098111) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

ABB, formed in 1988 and headquartered in Zurich, covers an unusually long stretch of a plant's equipment list, from the flowmeter and analyzer in the field to the drive, breaker and protection relay in the electrical room.

Seven Star LLC is an independent supplier serving Oman and the GCC. Our ABB listing concentrates on measurement and analytics: ABB flowmeters, liquid analysis sensors and systems, level and pressure instruments. It also includes valve actuators, low voltage circuit breakers, ABB drives, soft starters and protection relays.

ABB product families on this page

Flow measurement includes ABB electromagnetic, Coriolis, vortex and swirl meters, sold under names such as ProcessMaster, AquaMaster, CoriolisMaster and SwirlMaster. Liquid analysis covers pH, conductivity and dissolved oxygen sensors with their transmitters. SensyTemp TSP sensors handle temperature. On the electrical side the listing has ACS355 machinery drives, the ACS550 general purpose drive, the ACQ580 for water and wastewater and the ACS880-01 industrial drive, with fieldbus adapters such as the FPBA-01 for PROFIBUS DP. Protection and switching products include SACE Tmax XT molded case breakers, SACE Emax 2 air circuit breakers, PSR soft starters and the REM615 and RET615 relays.

Where ABB instruments and drives are used

Water and wastewater plants use the electromagnetic flowmeters, analyzers and ACQ580 drives together. Oil and gas, power and chemical plants specify the Coriolis and vortex meters, pressure and level transmitters and the 615 series relays for motor and transformer feeders. The drives run pumps, fans, conveyors and compressors in almost every industry.

Ordering ABB parts: what we need

For drives send the full type code from the rating label, for example ACS355-03E-05A6-4, plus the serial number if it is a replacement. For instruments send the complete order code, measuring span, process connection, wetted materials, output or protocol and the hazardous area approval. For breakers give frame size, rated current, breaking capacity, number of poles, trip unit and fixed or withdrawable version.

Frequently Asked Questions

What does 061A mean in ACS880-01-061A-3?
It is ABB's size code for this ACS880-01 type, equal to 61 A nominal output current in the -3 (380 to 415 V) voltage range.
Which frame size is ACS880-01-061A-3?
ABB lists it as frame R4. The IP21 enclosure is 203 mm wide, 580 mm high, 274 mm deep and weighs 18.6 kg.
What fuse does the manual give for ACS880-01-061A-3?
A 80 A gG fuse of ABB type OFAF000H80; the aR alternative is Bussmann 170M1567 at 100 A, and UL installations use JJS-80.
Does ACS880-01-061A-3 include a brake chopper?
Yes. ABB builds a brake chopper into frames R1 to R4 as standard.
What should I send for a ACS880-01-061A-3 quotation?
The full type code with plus codes, quantity, supply voltage, motor current, duty cycle and enclosure requirement. Seven Star LLC confirms availability and lead time with the quotation.