Brand:

FEP IDS Card IDS CU-88A, order code: 160050560

Description

Overview

The FEP CU-88A CPU module (IDS CU-88A), order code 160050560, is the central processing module of the IDS 850 Control Remote Action and Automation Technology system. It is responsible for the recording and archiving of process information, control of the input/output modules, operation of the communication interfaces, and the processing of internal control and regulation programs.

The module provides a 10/100 Ethernet connection and four serial interfaces, with connection to the modules in the system frame via the parallel system bus.

Engineering & Design

Data can be exchanged with coprocessor and network modules designed for this purpose via an additional serial bus (synchronous, HDLC). The module consists of two boards plugged onto one another: the base board contains all operating and display elements, the network, communication, and parameterisation/diagnostic interfaces, an SRAM buffered with a maintenance-free GoldCap, a real-time clock also buffered with a GoldCap, the watchdog logic (WDT), and the connection to the system bus 850.

The plug-in board contains the processor core with an MPC8247 PowerPC, the flash and SDRAM memory, a high-precision quartz oscillator, and the complete other functional logic.

Key Features

  • CPU module for IDS 850 systems
  • Order code 160050560
  • Recording and archiving of process information
  • Control of input/output modules
  • 10/100 Ethernet and four serial interfaces
  • Parallel system bus connection
  • Synchronous HDLC serial bus for coprocessors
  • MPC8247 PowerPC processor core
  • GoldCap-buffered SRAM and real-time clock
  • Watchdog logic (WDT)

Applications

  • Substation control and automation
  • Telecontrol data processing
  • I/O module control in IDS 850 frames
  • Process information recording
  • IDS 850 system expansion and spares

Specifications

Specification Value
Manufacturer FEP
Model CU-88A
Order Code 160050560
Type CPU module
Processor Core MPC8247 PowerPC
Network 10/100 Ethernet
Serial Interfaces 4
System Bus Parallel bus 850 + synchronous HDLC
Memory SRAM (GoldCap buffered), flash, SDRAM
Supervision Watchdog logic (WDT), real-time clock

Substation automation depends on reliable processing, and the FEP CU-88A CPU module provides it, which is why Seven Star LLC recommends the FEP CU-88A CPU module for IDS 850 systems.

The FEP IDS CU-88A CPU module is the central processor of the IDS card system and runs the measuring tasks of the connected I/O cards. The module is inserted in the first slot of the IDS station and the firmware is loaded over the serial interface. The processor communicates with the visualization system over the Ethernet link, and the slot status is indicated on the front panel.

The CU-88A CPU runs the cyclic measurement of the connected cards and the results are announced to the host system over the network link. The slot address and the station number are configured on the front switch for the identification of the station. The processor memory keeps the configuration without the battery and the parameters are restored after the power interruption. The spare CPU is exchanged while the wiring of the station remains untouched.

The CU-88A CPU module is used in the IDS compact stations where the measurement tasks of the I/O cards are coordinated by the single processor. The configuration is stored in the flash memory of the module and the station restarts without the external program load. The event log of the CPU records the power and the communication events for the troubleshooting.

Why Seven Star LLC

Seven Star LLC supplies the FEP IDS CU-88A CPU module for IDS 850 systems across the Gulf, with verified order codes and technical support. Our team assists with module selection and system configuration for substation automation projects.

We support energy, utility, and industrial automation customers with reliable B2B supply of telecontrol spares throughout the GCC.

System Performance

The CU88A’s processing functions cover process data recording, I/O control, and communication, centralising the automation duties of the IDS 850 system in one module. The MPC8247 PowerPC core and GoldCap-buffered SRAM provide dependable operation without battery maintenance.

The watchdog logic monitors the module’s health and the synchronous HDLC bus connects coprocessor and network modules, giving the system a structured and extensible architecture.

Identifying the CU-88A Module in Your IDS 850 Rack

Before ordering a replacement CPU for an IDS 850 station, read the module label and the station records. The most important identifiers are:

  • The module designation CU-88A and the order code 160050560 printed on the module.
  • The hardware revision and firmware version, because the configuration and parameter files for the station depend on the firmware.
  • Any coprocessor or network modules connected over the synchronous HDLC bus, which must be supported by the replacement CPU.
  • The communication interfaces in use, including the Ethernet link and the serial ports connected to protocol lines, service tools or local devices.

Replacement and Commissioning

Make a backup of the station parameters and project data with the engineering tool before starting. Isolate the station according to the utility’s switching and work permit rules, as telecontrol outputs may operate substation equipment. Label all interface cables, remove the old module and insert the new one in the same slot. After power-up, load the firmware and parameters that match the station configuration. Then check that the system bus modules are recognised and the communication links to the control centre are restored. Finally, verify a selection of indications, measurements and commands end to end before returning the station to normal operation.

Troubleshooting Guidance

  • Use the front panel display and status elements, together with the diagnostic interface, to find out whether a fault lies in the CPU, an I/O module or a communication line.
  • Repeated watchdog restarts can be caused by supply problems or overheating, so check the power supply and cabinet ventilation.
  • If data or time stamps are lost after a power outage, check the GoldCap-buffered SRAM and the real-time clock.

Applications in Oman and the GCC

IDS 850 telecontrol and automation systems are used in electrical substations and utility networks, where remote stations report to a central control room. Utilities and industrial operators with installed IDS equipment in the region rely on the FEP CU-88A CPU module to keep these stations in service until planned upgrades.

Sourcing from Seven Star LLC

Seven Star LLC supplies IDS 850 CPU and I/O modules for maintenance spares and urgent repairs. Share the order code, revision and firmware details, and we will confirm the module before dispatch.

Request a Quote for FEP IDS Card IDS CU-88A, order code: 160050560

For the FEP CU-88A CPU module, IDS 850 CPU module or any related control and instrumentation requirement, contact the Seven Star LLC team. Submit a formal inquiry through our RFQ page with your module, I/O and system configuration, and our specialists will respond with a detailed commercial proposal and the official FEP documentation.

Related Products

Datasheets & Documents
  • PDF Datasheet IDS GmbH FEP IDS Card IDS CU-88A, order code: 160050560 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Many utility outstations in the region still report to their control center through an IDS 850 telecontrol rack. IDS GmbH, founded in 1975 in Ettlingen, Germany, made its name with telecontrol and substation automation for power, gas and water networks, and today appears under the VIVAVIS name. Seven Star LLC lists IDS 850 cards and modules and supplies these spare cards to utilities and pipeline operators in Oman as an independent supplier.

IDS 850 cards and modules listed here

The page covers plug-in cards for the IDS 850 system as they appear in customer requests:

  • CC-88A and CU-88A cards (order codes 160050559 and 160050560)
  • EC86A Ethernet controller for IDS 850
  • RC8DA card (160050037) and SM85A signal module

Each card has a type name and a nine-digit order code, and both are printed on the card. For current projects the manufacturer offers the ACOS 7 series of telecontrol and automation units, with the modular ACOS 750 and the smaller ACOS 730.

Where IDS telecontrol equipment is used

The manufacturer serves electricity, gas, water and wastewater networks with control technology, station automation and metering. Typical locations are transformer and switching stations, pumping stations, reservoirs and pressure regulating stations spread over a large area. Operators in the GCC who still run IDS 850 racks normally ask for like-for-like cards.

Ordering IDS cards: what we need

Spare cards for a running telecontrol station must match in hardware and firmware. Send the card type and the order code, the hardware revision and firmware version if they are marked on the label, and a photo of the front and the component side. Tell us the station type and which neighboring cards are fitted in the rack. If a card is no longer produced, we check with the manufacturer's documentation which replacement it names and report that before you decide.

Frequently Asked Questions

What is the CU-88A?
It is the CPU module of the IDS 850 system, responsible for recording and archiving process information, controlling I/O modules, and processing control programs.
What is the order code?
The order code is 160050560.
Which processor is used?
The plug-in board contains an MPC8247 PowerPC core with flash and SDRAM memory.
What interfaces does it provide?
It provides a 10/100 Ethernet connection, four serial interfaces, and the parallel system bus connection.
What is the GoldCap used for?
It buffers the SRAM and real-time clock, maintaining data without battery maintenance.