Brand: SAUTER
Sauter NRFC413MF111 Modbus Fan Coil Thermostat 0-10 V 2-Pipe
Description
The NRFC413MF111 is a Sauter Modbus RTU room thermostat for 2-pipe fan coil units. It drives a 0 to 10 V valve actuator, usually on a pressure-independent control valve, controls a 3-speed fan through three relays and reports the valve position back to the building management system, all on a 100 to 240 V supply and a 14 mm slim housing.
A fan-coil thermostat that talks Modbus
The NRFC4 range is Sauter’s single-room controller for fan coil units in commercial and residential buildings. The NRFC413MF111 is the variant for 2-pipe systems with continuous valve control: it compares the integrated room-temperature measurement with the setpoint, opens the valve in heating or cooling mode and steps the 3-speed fan according to the deviation. Because it has a Modbus/RTU interface, hotel rooms, offices or student housing can be tied into one network and managed centrally.
Key features from the datasheet
- Valve control with 0 to 10 V output; positional feedback signal can be sent to the BMS over Modbus
- For a valve with dynamic hydronic balancing (PICV) and 0 to 10 V actuator control
- Large configurable LCD with backlight; six buttons; integrated on/off timer; button lock for public installations
- Automatic summertime/wintertime changeover in 2-pipe systems with an NTC cable sensor on the supply pipe
- Digital input assignable as presence signal, dew-point monitor or filter fault signal
- Fitting plate installation without opening the controller; installation height 14 mm
Technical specification
| Parameter | Specification |
|---|---|
| Type | NRFC413MF111 |
| Application | 2-pipe, continuous, with positional feedback signal |
| Fan | 3 speeds |
| Power supply | 100 to 240 VAC, 50/60 Hz |
| Power consumption | 5 VA |
| Temperature input | 1 × NTC 10k |
| Analogue input | 1 × 0 to 10 V (valve feedback) |
| Digital input | 1 (closed below 0.3 VDC, open above 0.7 VDC) |
| Analogue output | 1 × 0 to 10 V (100 kΩ) |
| Relay outputs | 3 × single-pole normally open; 2.2 A (IR), 3.6 A (IX), cos φ 0.98 at 240 VAC |
| Interface | RS-485, Modbus/RTU, 3-pin screw terminal, 4800 or 9600 bit/s |
| Modbus address range | 1 to 64 |
| Function codes | 01, 03, 04, 06, 16; CRC-16; data type u16; 10-bit frame, no parity |
| Display / buttons | LCD with adjustable backlight / 6 |
| Ambient temperature / humidity | 0 to 40 °C / 10 to 90 % rh, no condensation |
| Storage and transport | -10 to 60 °C |
| Dimensions W × H × D | 88 × 88 × 46.2 mm |
| Weight | 0.3 kg |
| Housing | Polycarbonate, white; fits round or square recessed box |
| Type of protection / class | IP20 (EN 60529) / II (IEC 60730) |
| Conformity listed | EMC 2014/30/EU, Low-Voltage 2014/35/EU (EN 60730-1, EN 60730-2-9), RoHS |
Selection and ordering guide
Four types share the same hardware family; pick by pipe system, valve type and fan motor.
| Order code | System | Valve control | Fan | Relays / AO |
|---|---|---|---|---|
| NRFC413MF111 | 2-pipe | Continuous 0-10 V, with feedback | 3 speeds | 3 relays, 1 AO |
| NRFC422MF111 | 2- or 4-pipe | 2-point | 3 speeds | 5 relays |
| NRFC423MF111 | 2- or 4-pipe | Continuous | 3 speeds | 3 relays, 2 DI |
| NRFC424MF112 | 2/4-pipe 2-point or 2-pipe continuous | 2-point or 0-10 V | EC motor with cut-off | 3 relays, 2 DI |
Installation and commissioning notes
- Mount on a 60 mm recessed box at 140 to 150 cm height and keep it away from heat sources, direct sun, draughts, room corners, curtains and shelving.
- Seal empty installation tubes; air flowing out of them causes false temperature readings.
- Wiring: mains and relay terminals take 1.0 to 1.5 mm²; signal terminals 0.14 to 1.5 mm²; protect the L supply with an external 5 A slow-blow fuse.
- Keep the RS-485 cable separate from live installation wiring; up to 32 NRFC4 devices can sit on one Modbus line.
- After commissioning allow up to one hour for thermal balance in the room before judging the reading.
- Not for safety applications, outdoor or condensing areas, or vibrating installations such as ships.
Applications in Gulf building services
Fan coil units are the standard terminal device in Oman and the wider GCC, from hotels and hospitals to residential towers on district cooling. A 2-pipe fan coil with a 0 to 10 V PICV is a common arrangement, and the Modbus link lets facility teams see room temperature and valve position and switch rooms off when unoccupied. The NRFC413MF111 therefore targets hospitality and multi-unit buildings where per-room control and central visibility matter; the datasheet confines it to indoor use.
Selection and installation notes
A building automation device is selected from the signal type, the supply voltage, the mounting position and the system it connects to. Check the wiring diagram and the cable type, keep sensor cables away from power wiring, confirm the addressing or scaling in the controller, test each point at commissioning and record the final settings. Use the mounting accessories and the installation position given in the data sheet.
For a Modbus thermostat, set the address, baud rate and parity to match the network, and check the valve and fan outputs before handover.
Information needed for a quotation
Send the full model code, the quantity, the delivery location in Oman or the GCC, the intended use and any accessories needed, so that the complete package can be quoted together.
Documents and supply information
The manufacturer data sheet is attached to this page and should be read together with the project specification and the site risk assessment before a purchase is confirmed. Ratings, standards and dimensions are quoted as printed on that sheet. Lead time, stock position and certificates available with the shipment are confirmed in the quotation, and we supply to Oman and the wider GCC region for industrial, utility and building services projects.
Accessories and related items
The datasheet describes a connectable NTC 10k cable temperature sensor, which can serve as the remote room sensor or as the supply-pipe changeover sensor in 2-pipe systems; the internal sensor is deactivated automatically when a cable sensor is used. The controller also works with a 0 to 10 V actuator on a pressure-independent control valve, and the related fitting instructions are P100019338. Ask for exact sensor and valve part numbers to suit the project.
Frequently asked questions
Which fan coil systems does the NRFC413MF111 suit?
2-pipe systems with a continuous 0 to 10 V valve actuator, typically on a PICV, and a 3-speed fan.
How does it connect to a building management system?
Through RS-485 using Modbus/RTU at 4800 or 9600 bit/s, with addresses 1 to 64; function codes 01, 03, 04, 06 and 16 are supported.
Can it detect heating or cooling changeover?
Yes. With an NTC cable sensor on the supply pipe it detects summertime or wintertime operation automatically in a 2-pipe configuration.
Can it control an EC-motor fan?
No. The NRFC413MF111 drives a 3-speed fan through relays. The NRFC424MF112 is the type with the EC-motor output.
Who supplies the NRFC413MF111 in Oman?
Seven Star LLC is an independent supplier in Muscat and quotes against the exact order code. Confirm valve type, fan and bus requirements before ordering.
Documents and quotation
The official Fr. Sauter AG product data sheet 43.078 for the NRFC 413 and 422 to 424 (2025) is linked on this page. Send the order code and quantity to request a quotation. See more in Controllers & Data Acquisition.
Datasheets & Documents
- Datasheet Sauter NRFC 413, 422...424 product data sheet 43.078 (PDF, 2025) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
SAUTER is a Swiss building automation company based in Basel and active since 1910. The group designs and manufactures control valves, actuators, sensors, thermostats and room controllers for heating, ventilation and air conditioning in commercial, industrial and public buildings.
Seven Star LLC is an independent supplier in Muscat. We list SAUTER field devices against exact order codes and the official SAUTER data sheets, for HVAC contractors and facility teams in Oman and the GCC.
SAUTER product series
Valves and actuators include the VUG050F304 DN50 flanged control valve, the VKAI032F300 DN32 cut-off ball valve, the AKM115F120 rotary actuator for ball valves and the ASF112F222 spring-return damper actuator.
Sensors and controllers include the EGP100F412 differential pressure transducer, the EGQ222F032 CO2 and temperature room transducer, the EGT346F103 Ni1000 duct temperature sensor and the NRFC413MF111 Modbus fan coil thermostat. Safety devices include the TUC407F001 safety temperature limiter to EN 14597 and the DSF158F001 stainless pressure switch with SIL 2.
Where SAUTER products are used
Air handling units and fan coils, chilled and hot water circuits, boiler plants and room control in hotels, hospitals, offices, schools and laboratories connected to a building management system.
Ordering SAUTER products: what we need
Send the full SAUTER order code, such as VUG050F304. If unknown, give the valve size, Kvs and pressure rating, the actuator torque or force, control signal and supply voltage, and for sensors the range, output and mounting.
Browse SAUTER products by category: Valve Actuators.
Related products
Frequently Asked Questions
2-pipe systems with a continuous 0 to 10 V valve actuator, typically on a PICV, and a 3-speed fan.
Through RS-485 using Modbus/RTU at 4800 or 9600 bit/s, with addresses 1 to 64; function codes 01, 03, 04, 06 and 16 are supported.
Yes. With an NTC cable sensor on the supply pipe it detects summertime or wintertime operation automatically in a 2-pipe configuration.
No. The NRFC413MF111 drives a 3-speed fan through relays. The NRFC424MF112 is the type with the EC-motor output.
Seven Star LLC is an independent supplier in Muscat and quotes against the exact order code. Confirm valve type, fan and bus requirements before ordering.

Reviews
There are no reviews yet.