Brand:

ABB ACH580-01-293A-4 HVAC AC Drive 160 kW 293 A

Description

Where the ACH580-01-293A-4 fits in a building

The 160 kW rating belongs to frame R8, used for large chiller-plant pumps and tunnel or car-park fans. The catalogue type that matches is the ACH580-01-293A-4: three-phase, 160 kW typical motor power, 293 A nominal current, frame R8. It is the HVAC-optimised sibling of ABB’s general purpose drive and keeps the same all-compatible platform, so panels, PC tools and fieldbus adapters carry over.

Software separates it from a general purpose drive: the HVAC program supplies Drivetune smartphone commissioning with the Bluetooth panel, override (fire) mode, four start interlocks and belt-loss (under-load) detection. Browse neighbouring ratings in AC drives or read the general ABB ACS580 overview for the sister platform.

Technical specifications

Parameter Specification
Order type ACH580-01-293A-4
Family and mounting ACH580 HVAC series, 01 = wall-mounted
Mains voltage class Three-phase 380 to 480 V, code 4
Frame R8
Nominal output at 400 V 160 kW, 293 A
Light-duty output at 400 V 278 A, 160 kW
Light-duty output at 480 V 260 A, 200 hp
Protection class IP21 (UL Type 1), or IP55 (UL Type 12) via +B056
IP21 height, width, depth 965 mm with gland box (680 mm without) x 300 x 393 mm
Mass in IP21 69 kg
IP55 size and mass 965 x 300 x 452 mm, 77 kg
Adjacent catalogue types Below: ACH580-01-246A-4 (132 kW); above: ACH580-01-363A-4 (200 kW)

Choosing between 400 V and 480 V data

The catalogue gives three ratings for this type. Nominal use is 293 A for 160 kW. Light-duty use on 380 to 415 V is 278 A for 160 kW, which allows 110% overload for one minute in ten (about 305.8 A, derived). On a 440 to 480 V supply the light-duty current is 260 A, matching 200 hp. ABB states that all ACH580 ratings apply at +40 degrees C ambient.

Frame R8 in IP21 form stands 965 mm tall including the gland box (680 mm without it), 300 mm wide and 393 mm deep, and weighs 69 kg. The IP55 build measures 965 x 300 x 452 mm at 77 kg. The catalogue lists no switch or C1 variant for frames above R5.

Motor pairing from the catalogue: the ACH580-01-293A-4 is listed with 132 kW M3BL315SMB4 at 1500 rpm (290 A nominal, motor efficiency 96.4%, package efficiency 94.0%) in the IE4 synchronous reluctance (SynRM) selection guide. The efficiency figures are ABB’s calculated drive-plus-motor values and do not promise the same result with a different motor.

Type code and option codes

An order line starts with ACH580-01-293A-4: 01 marks the wall-mounted drive, 293A is the rating field and 4 the voltage class. Typical plus codes are +L523 for CMOD-02 with an isolated PTC interface, +L512 for CHDI-01 with 115/230 V inputs, +B056 for IP55 and +F278 for a main disconnect switch with auxiliary contact.

Beyond the built-in protocols, the catalogue pairs plus codes with adapters, for instance POWERLINK via FEPL-02 (+K470), BACnet/IP via FBIP-21 (+K465) and Modbus TCP via FMBT-21 (+K491).

Catalogue data for the family includes a DC choke built to IEC 61000-3-12, Safe Torque Off certified to SIL 3 / PL e, an EMC category C2 design for frames R1 to R9, six digital inputs and two analog inputs and two analog outputs and three relay outputs.

Documents and quotation

Request the ACH580-01-293A-4 from Seven Star LLC with your motor nameplate, supply voltage and communication needs; the quotation gives availability and lead time. Ratings, dimensions, motor pairing and option codes on this page were taken from ABB catalogue 3AUA0000186691, revision F (9.14.2019), available via the document link.

Confirm before ordering: type code and plus options, motor rated current, enclosure class, ambient temperature and altitude, and any change in newer ABB documents.

Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

ABB, formed in 1988 and headquartered in Zurich, covers an unusually long stretch of a plant's equipment list, from the flowmeter and analyzer in the field to the drive, breaker and protection relay in the electrical room.

Seven Star LLC is an independent supplier serving Oman and the GCC. Our ABB listing concentrates on measurement and analytics: ABB flowmeters, liquid analysis sensors and systems, level and pressure instruments. It also includes valve actuators, low voltage circuit breakers, ABB drives, soft starters and protection relays.

ABB product families on this page

Flow measurement includes ABB electromagnetic, Coriolis, vortex and swirl meters, sold under names such as ProcessMaster, AquaMaster, CoriolisMaster and SwirlMaster. Liquid analysis covers pH, conductivity and dissolved oxygen sensors with their transmitters. SensyTemp TSP sensors handle temperature. On the electrical side the listing has ACS355 machinery drives, the ACS550 general purpose drive, the ACQ580 for water and wastewater and the ACS880-01 industrial drive, with fieldbus adapters such as the FPBA-01 for PROFIBUS DP. Protection and switching products include SACE Tmax XT molded case breakers, SACE Emax 2 air circuit breakers, PSR soft starters and the REM615 and RET615 relays.

Where ABB instruments and drives are used

Water and wastewater plants use the electromagnetic flowmeters, analyzers and ACQ580 drives together. Oil and gas, power and chemical plants specify the Coriolis and vortex meters, pressure and level transmitters and the 615 series relays for motor and transformer feeders. The drives run pumps, fans, conveyors and compressors in almost every industry.

Ordering ABB parts: what we need

For drives send the full type code from the rating label, for example ACS355-03E-05A6-4, plus the serial number if it is a replacement. For instruments send the complete order code, measuring span, process connection, wetted materials, output or protocol and the hazardous area approval. For breakers give frame size, rated current, breaking capacity, number of poles, trip unit and fixed or withdrawable version.

Frequently Asked Questions

What are the light-duty ratings of the ACH580-01-293A-4?
ABB lists 278 A for 160 kW on a 380 to 415 V network and 260 A for 200 hp on a 440 to 480 V network, with a nominal rating of 293 A.
Which frame size and weight does the ACH580-01-293A-4 have?
It is frame R8. In IP21 it weighs 69 kg and measures 300 x 393 mm in width and depth; the IP55 version weighs 77 kg.
How is the IP55 version of the ACH580-01-293A-4 ordered?
Add the plus code +B056 to the type designation. The catalogue calls it the IP55 unit for wall-mountable drives and lists 965 x 300 x 452 mm for frame R8.
Which building-automation protocols are built into the ACH580-01-293A-4?
BACnet MS/TP, Modbus RTU and N2 are included as standard. BACnet/IP and other networks need an F-series adapter, for example FBIP-21 with +K465.
Which motor does ABB pair with the ACH580-01-293A-4?
The catalogue lists ACH580-01-293A-4 as matched drive for 132 kW M3BL315SMB4 at 1500 rpm.