Brand: MOXA
Moxa NPort IA5150A 1-Port Serial Device Server
Description
What the NPort IA5150A gives a serial instrument
A DIN-rail serial device server for automation panels with serial, LAN and power surge protection and two 10/100 Ethernet ports that share one IP address, so panels can be daisy-chained without an extra switch. Moxa’s own one-line description of the NPort IA5150A reads: 1-port RS-232/422/485 industrial automation device server with serial/LAN/power surge protection, 2 10/100BaseT(X) ports with single IP, 0 to 60°C operating temperature.
Key figures from the Moxa page: the power input is 12 to 48 VDC; operating temperature is 0 to 60°C (32 to 140°F); dimensions are 36 x 105 x 140 mm (1.42 x 4.13 x 5.51 in); weight is 475 g (1.05 lb).
Standards and approvals printed for this model include hazardous-location listings of ATEX Zone 2; UL/cUL Class I Division 2 Groups A/B/C/D; safety standard UL 508. Approvals can differ between variants of a series, so check the one on the exact order code.
Technical specifications
| Parameter | Specification |
|---|---|
| 10/100BaseT(X) Ports (RJ45 connector) | Supports 2 IP addresses; Auto MDI/MDI-X connection |
| Magnetic Isolation Protection | 1.5 kV (built-in) |
| Management | ARP; BOOTP; DHCP Client; DNS; HTTP; HTTPS; ICMP; IPv4; LLDP; Rtelnet; SMTP; SNMPv1/v2c; TCP/IP; Telnet; UDP |
| Filter | IGMP v1/v2 |
| Time Management | SNTP |
| Authentication | Local database |
| Encryption | HTTPS; AES-128; RSA-1024; SHA-1; SHA-256 |
| Connector | DB9 male for RS-232; Terminal block for RS-422/485 |
| No. of Ports | 1 |
| Serial Standards | RS-232; RS-422; RS-485 |
| Operation Modes | Disabled; Ethernet Modem; Pair Connection; Real COM; Reverse Telnet; RFC2217; TCP Client; TCP Server; UDP |
| Baudrate | Supports standard baudrates (unit=bps): 50, 75, 110, 134, 150, 300, 600, 1200, 1800, 2400, 4800, 7200, 9600, 19200, 38400, 57600, 115200, 230.4k, 460.8k, 921.6k |
| Data Bits | 5, 6, 7, 8 |
| Stop Bits | 1, 1.5, 2 |
| Parity | None, Even, Odd, Space, Mark |
| Flow Control | None; RTS/CTS (RS-232 only); DTR/DSR (RS-232 only); XON/XOFF |
| Pull High/Low Resistor for RS-485 | 1 kilo-ohm, 150 kilo-ohms |
| Terminator for RS-485 | 120 ohms |
| RS-485 Data Direction Control | ADDC (automatic data direction control) |
| RS-232 | TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND |
| RS-422 | Tx+, Tx-, Rx+, Rx-, GND |
| RS-485-4w | Tx+, Tx-, Rx+, Rx-, GND |
| RS-485-2w | Data+, Data-, GND |
| Input Current | 220 mA @ 12 VDC |
| Input Voltage | 12 to 48 VDC |
| No. of Power Inputs | 2 |
| Power Connector | Terminal block |
| Housing | Metal |
| Dimensions | 36 x 105 x 140 mm (1.42 x 4.13 x 5.51 in) |
| Weight | 475 g (1.05 lb) |
| Installation | DIN-rail mounting; Wall mounting (with optional kit) |
| Operating Temperature | 0 to 60°C (32 to 140°F) |
| Storage Temperature (package included) | -40 to 75°C (-40 to 167°F) |
| Ambient Relative Humidity | 5 to 95% (non-condensing) |
| EMC | EN 55032/35 |
| EMI | CISPR 32, FCC Part 15B Class A |
| Hazardous Locations | ATEX Zone 2; UL/cUL Class I Division 2 Groups A/B/C/D |
| Safety | UL 508 |
| Vibration | IEC 60068-2-6 |
| Shock | IEC 60068-2-27 |
| Freefall | IEC 60068-2-32 |
| Green Product | RoHS, CRoHS, WEEE |
| Warranty Period | 5 years |
Where it fits and what to check
It suits control cabinets that bring a single serial instrument onto the plant network and need to pass the Ethernet line on to the next device.
On the practical side, mounting is listed as din-rail mounting; wall mounting (with optional kit); the housing is metal; the stated MTBF is 262,805 hrs; the warranty period is 5 years. Treat the MTBF as a manufacturer prediction under its stated method, not a guarantee for your site.
What to confirm before ordering: the IEX version listed in the series for hazardous-area use, and the temperature grade. Our team in Muscat works from the exact code on your enquiry, as an independent supplier.
Related models in the NPort IA5150A family
The Moxa product list shows these models in the same family page (20 entries): NPort IA5150A, NPort IA5150A-IEX, NPort IA5150A-T, NPort IA5150A-T-IEX, NPort IA5150AI, NPort IA5150AI-IEX, NPort IA5150AI-T, NPort IA5150AI-T-IEX, NPort IA5250A, NPort IA5250A-IEX, NPort IA5250A-T, NPort IA5250A-T-IEX, NPort IA5250AI, NPort IA5250AI-IEX, NPort IA5250AI-T, NPort IA5250AI-T-IEX, NPort IA5450A, NPort IA5450A-T, NPort IA5450AI, NPort IA5450AI-T. Suffixes such as -T generally mark wide-temperature versions and fiber suffixes (M, S, MM, SS with SC or ST) mark the connector and fiber type, but the order code printed on the datasheet governs.
Documents and quotation
The attached file is Moxa’s published datasheet for the family (moxa-nport-ia5000a-series-datasheet-v1.6). For a quotation, send the full order code, the quantity required and where the goods are to be delivered.
More products in this range: Industrial Communications.
Datasheets & Documents
- Datasheet Moxa NPort IA5000A series datasheet v1.6 Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Since 1987 Moxa, based in New Taipei City, Taiwan, has built networking hardware for places where an office switch would fail: substations, wellhead panels, roadside cabinets. Seven Star LLC lists Moxa industrial Ethernet switches and fiber converters and supplies Moxa networking devices to system integrators and plant teams in Oman as an independent supplier. Each request is checked against the full Moxa model name before we quote.
Moxa switches and converters listed here
The EDS-G508E is a managed switch with eight Gigabit ports from the EDS managed line. The EDS-316-MM-SC-T is a 16-port unmanaged switch with 14 copper ports, two multi-mode SC fiber ports and the wide-temperature option (-40 to 75 C). The TCF-142-S-SC-T belongs to the TCF-142 series, which converts RS-232/422/485 serial signals to single-mode fiber. Moxa also makes serial device servers, protocol gateways, wireless devices and industrial computers, used on SCADA and telemetry networks across the GCC.
Ordering Moxa devices: what we need
The suffixes carry the specification. Send the complete model name, including fiber mode and connector (MM-SC, SS-SC, ST), the -T wide-temperature suffix and any coating or approval suffix. Add the power supply voltage, the SFP modules needed and the quantity.
Browse MOXA products by category: Industrial Communications.
Related products
Frequently Asked Questions
Moxa lists it as: 1-port RS-232/422/485 industrial automation device server with serial/LAN/power surge protection, 2 10/100BaseT(X) ports with single IP, 0 to 60°C operating temperature. A DIN-rail serial device server for automation panels with serial, LAN and power surge protection and two 10/100 Ethernet ports that share one IP address, so panels can be daisy-chained without an extra switch.
The Moxa specification gives an input voltage of 12 to 48 VDC. Check the terminal arrangement and, where relevant, the redundant-input wiring against your panel supply before ordering.
The listed operating temperature is 0 to 60°C (32 to 140°F). Wide-temperature versions carry a -T suffix in Moxa's order codes where the series offers them, and they are separate order codes.
The datasheet lists RS-232; RS-422; RS-485 on DB9 male for RS-232; Terminal block for RS-422/485, with 1 serial port(s).
You can download the Moxa datasheet from this page. For a quotation, send us the full order code, quantity and destination; Seven Star LLC is an independent supplier based in Muscat.