- Vibration Monitoring
- Industrial Communications
- PLC & I/O Cards
- Automation Accessories
- Controllers & Data Acquisition
- AC Drives
- Industrial Computers
- Encoders
- Safety Switches & Guard Locking
- Isolator & Barrier
- Automation Software
- HMI Displays
- CCTV & Security
- Motor Soft Starters
- Servo Drives
- Robotics
- Pneumatic Cylinders
- Machine Vision
Brand: DEIF
DEIF AGC-4 Mk II Genset, Mains, BTB, Group and Plant Controller
Description
Configurable controller from single genset to plant management
The DEIF AGC-4 Mk II is a configurable controller for a wide range of applications. It contains the three-phase measuring circuits and all functions needed to protect and control a genset, and the same family also protects and controls mains connections, tie breakers and bus tie breakers. A single controller can run one genset, controllers can share load with CANshare or PMS lite, and in a full power management system up to 40 AGC-4 Mk II controllers can be connected.
DEIF lists the AGC-4 Mk II in combination with AGC-4, iE 150, AGC 150 (up to 32), ASC 150 solar and storage controllers and ALC-4 load controllers. With extended power management a system can handle up to 992 gensets. Plant modes include automatic mains failure, fixed power, peak shaving, load takeover and mains power export, and all modes can be combined with AMF.
Technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / model | DEIF, AGC-4 Mk II (data sheet software version 6.23) |
| Variants | 01 Genset, 02 Mains, 03 BTB, 04 Group, 05 Plant controller |
| Auxiliary supply | 12/24 V DC nominal, 8 to 36 V DC operating; terminals 1-2 max 11 W, terminals 98-99 max 5 W |
| Voltage measurement | 100 to 690 V nominal; accuracy ±0.5 % or ±0.5 V (low range); UL/cUL 600 V AC phase-phase |
| Current measurement | 1 A or 5 A nominal; accuracy ±0.5 % or ±5 mA (low) / ±25 mA (high); 10 A continuous |
| Frequency | 10 to 75 Hz measurement; system frequency accuracy ±10 mHz within 45 to 66 Hz |
| Digital inputs | Optocoupler, ON 8 to 36 V DC, impedance 4.7 kΩ |
| Relay outputs | 250 V AC / 30 V DC, 5 A electrical rating; 2 A continuous at 50 °C |
| Analogue outputs | 0(4) to 20 mA and ±25 mA, galvanically separated |
| RPM input | MPU 2 to 70 V AC, 10 to 10000 Hz |
| Operating temperature | -25 to +70 °C; storage -40 to +70 °C |
| Protection | Controller IP20; DU-2 display and AOP IP40 (IP54 with option L gasket) |
| Mounting | DIN rail or base mount with six screws |
| Weight | Controller 1.6 kg; DU-2 display or AOP 0.4 kg |
| Approvals listed | UL/cUL Listed to UL/ULC6200:2019 1st edition; EN/IEC 61010-1, 60255-27, 61000-6-2, 61000-6-4, 60255-26; IACS UR E10 vibration |
Displays, options and engine communication
The controller is operated from a TDU touch display or the DU-2 LCD display, with the AOP-1 and AOP-2 additional operator panels available as options. Accessories include DU-2 display cables of 1, 3 and 6 m (J6, J1, J2), a USB PC cable (J7) and the RMB connector kit (J8). The ordering example in the data sheet shows the variant number and option letters, so the variant and options must be stated in an enquiry.
Hardware options include dual CAN (H12.8) for engine communication, DVC 550, 350 and 310 digital voltage controllers, external I/O and CANshare, an MTU ADEC option (H13), and 4 to 20 mA, relay and multi-input extension cards. The data sheet lists third-party digital load sharing with ComAp, DeepSea MSC7 and SmartGen controllers using option H12.
Selecting the AGC-4 Mk II
Choose the variant for the role of each controller, then the display, the engine interface, the power management scale and the extension options. Confirm whether a separate TDU is needed, because it is a separate product with its own data sheet. The newer AGC 150 covers many of the same roles in a compact housing, so compare it with this model when the project needs the AGC-4 Mk II platform for compatibility with an existing plant.
How the DEIF AGC-4 Mk II works
The controller measures the voltage, current and frequency of the genset and of the mains. It starts and stops the engine, closes and opens the breakers and shares the load with other sets. Its protections trip the set on faults. Each controller has its own task, genset, mains, tie breaker, group or plant, and the controllers talk over a network.
Where the AGC-4 Mk II is used
- Single gensets
- Stand-by sets with mains failure start
- Load sharing plants
- Peak shaving
- Plants with tie breakers and bus ties
Selection checklist for the AGC-4 Mk II
- Variant: genset, mains, BTB, group or plant
- Supply of 12/24 V DC
- Voltage and current ranges
- Digital inputs and relay outputs
- Display unit or AOP
- Engine communication
- Number of controllers in the plant
- Mounting method
Installation, commissioning and maintenance notes for the AGC-4 Mk II
Mount the controller on a DIN rail or a base with six screws. Wire the supply, the measurements and the breaker signals. Load the parameters with the PC software. Test the plant modes without load first. Check the alarm log after the first runs.
Requesting a quotation for the DEIF AGC-4 Mk II
Please send the variant, the options and the quantity. Seven Star LLC serves industrial customers in Oman and the GCC and replies with a quotation based on the information provided.
AGC-4 Mk II variants
The variants are 01 Genset, 02 Mains, 03 BTB, 04 Group and 05 Plant controller.
AGC-4 Mk II plant modes
The plant modes are automatic mains failure, fixed power, peak shaving, load takeover and mains power export.
AGC-4 Mk II power management
Up to 40 controllers can be linked, and extended power management handles up to 992 gensets.
AGC-4 Mk II supply
The auxiliary supply is 12/24 V DC, with an operating range of 8 to 36 V DC.
AGC-4 Mk II measurement
The voltage runs from 100 to 690 V and the frequency from 10 to 75 Hz.
AGC-4 Mk II relay outputs
The relay outputs are rated 250 V AC or 30 V DC at 5 A.
AGC-4 Mk II temperature range
The operating range is minus 25 to plus 70 degrees C.
AGC-4 Mk II protection and weight
The controller is IP20 and weighs 1.6 kg. The display unit is IP40 and weighs 0.4 kg.
Controller records for the AGC-4 Mk II
Record the parameter file, the software version and the date of each test.
Choosing the right AGC-4 Mk II variant
Choose one controller for each breaker or genset that the single-line diagram shows.
Documents and quotation
The attached DEIF data sheet is the full 46-page document. Send the variant, options, quantity and engine data for a quotation. See Diesel Generator Spare Parts for other generator control products.
Datasheets & Documents
- Datasheet DEIF AGC-4 Mk II data sheet 4921240614 (EN) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
DEIF is a Danish, family-owned and independent manufacturer of control and protection devices for power generation, founded in a Copenhagen backyard in 1933 and now based in Skive. Seven Star LLC, an independent supplier in Muscat, quotes DEIF AGC, SGC and CGC genset controllers for standby plants, paralleling systems and engine-driven sets.
DEIF genset and power management controllers
DEIF describes itself as a supplier of power control solutions for decentralised power generation on land and at sea. Its genset controllers range from the compact SGC and CGC units to the AGC 150 and AGC-4 Mk II controllers, which add synchronisation and power management for plants with many gensets. DEIF data sheets state the supply range, I/O, protections and approvals of each controller.
Ordering DEIF controllers
Name the exact model and variant, the software package or option letters where they apply, the quantity and the engine make and ECU protocol. DEIF configures several controllers by variant and option, so the data sheet on each page should be checked against the project before a quotation is issued.
Related products
Frequently Asked Questions
It is the Mk II version of the AGC-4. DEIF documents power management with up to 40 AGC-4 Mk II controllers and combinations with AGC-4, iE 150, AGC 150, ASC 150 and ALC-4 units.
Variant 01 Genset, 02 Mains, 03 BTB, 04 Group and 05 Plant controller, each with standard options listed in the data sheet.
Operation is from a TDU touch display or a DU-2 LCD display, which are ordered with the controller as separate items or options.
DIN rail or base mount with six screws, as listed in the environmental specifications.
The data sheet lists third-party digital load sharing with ComAp, DeepSea MSC7 and SmartGen controllers when option H12 is fitted.