- Vibration Monitoring
- Industrial Communications
- PLC & I/O Cards
- Automation Accessories
- Controllers & Data Acquisition
- AC Drives
- Industrial Computers
- Encoders
- Safety Switches & Guard Locking
- Isolator & Barrier
- Automation Software
- HMI Displays
- CCTV & Security
- Motor Soft Starters
- Servo Drives
- Robotics
- Pneumatic Cylinders
- Machine Vision
Brand: STAMFORD
STAMFORD AS480 Automatic Voltage Regulator (AVR)
Description
A compact SMT regulator with an excitation boost interface
The STAMFORD AS480 is a half-wave phase-controlled automatic voltage regulator for brushless generators. It uses surface-mount technology, custom mouldings and heatsinks to make a compact assembly, and adds a feature the smaller AVRs lack: a connection for the optional Excitation Boost System (EBS), used where short-circuit current has to be maintained on a self-excited machine.
The AVR is linked to the main stator windings and the exciter field to form a closed loop with load regulation of +/-1.0 percent, assuming 4 percent engine governing. Sensing and power inputs share one 100 to 264 V ac single-phase supply. Positive voltage build-up from residual levels is ensured by efficient semiconductors in the power circuit.
Technical specifications
| Parameter | Specification |
|---|---|
| Sensing and power input | 100-264 V ac, 1 phase, 50-60 Hz |
| Output voltage | 82 V dc at 200 V ac power input; 45 V dc at 110 V ac |
| Output current | 5 A continuous; 7.5 A transient for 10 s |
| Exciter field resistance | 15 ohms minimum |
| Regulation | +/-1.0% (with 4% engine governing) |
| Thermal drift | 0.03% per degree C change in AVR ambient (after 2 minutes) |
| System response | AVR 20 ms; field current to 90% 80 ms; machine volts to 97% 300 ms |
| External voltage adjustment | +/-10% with 1 k ohm, 1 W trimmer; fixed 15 k ohm resistor enables 110 V sensing |
| Under-frequency protection | Set point 94-98% Hz, jumper selectable 50/60 Hz |
| Quadrature droop input | 10 ohm burden; max sensitivity 0.07 A for 5% droop at 0 PF; max input 0.33 A |
| Over-excitation protection | Set point 67 V dc +/-3%, delay 10-15 s |
| Power dissipation | 12 W maximum |
| Operating temperature | -40 to +70 C (derate output 5% per degree C above 60 C) |
| Build-up voltage | 4 V at AVR terminals |
| Vibration / storage | 20-100 Hz 50 mm/s, 100 Hz-2 kHz 3.3 g; storage -55 to +80 C |
How the AS480 is set up
Stability links select the response of the damping circuit to suit the generator size, with separate link positions for sets above and below 100 kW. A slow response setting is offered for small sets, where it helps reduce lamp flicker. The red LED shows under-speed running and doubles as the over-excitation indicator. The over-excitation trip level is set at the works at 65 V dc and cannot be altered; the condition is allowed for approximately eight seconds so that normal transients and short-term overloads do not cause nuisance trips, and the generator must be stopped to reset it.
110 V sensing and the Excitation Boost System
Operation with 110 V ac sensing is possible by replacing the hand trimmer link with a fixed resistor, but the hand trimmer then cannot be used and generator overload capability is reduced. The EBS is a small externally mounted rotary power supply, short-term rated, that provides excitation in heavy overloads or short circuits; its own electronics protect the generator against sustained overload. Where the AVR is mounted outside the generator the manual says to derate by 20 percent.
Choosing among STAMFORD AVRs
The AS480 is a self-excited, single-phase sensed regulator. Use the table to compare it with its siblings before ordering.
How the STAMFORD AS480 works
The regulator senses the generator output voltage and compares it with a set point. It then adjusts the DC current it feeds to the exciter field. If the voltage falls, it raises the field current. If the voltage rises, it lowers it. In this way the generator voltage stays steady as the load changes. The optional boost system lets the machine keep short-circuit current.
Where the AS480 is used
- Brushless generator sets
- Self-excited machines
- Sets needing short-circuit current
- Small sets that need slow response
- Stand-by and prime power plants
Selection checklist for the AS480
- Supply of 100 to 264 V ac
- Output of 5 A continuous
- Exciter field resistance above 15 ohms
- 50 or 60 Hz setting
- Droop input for paralleling
- Excitation Boost System option
- External voltage trimmer
- Ambient temperature
Installation, commissioning and maintenance notes for the AS480
Mount the regulator on a firm surface with the heatsink free for air. Wire the sensing and power inputs and the exciter field. Select the frequency and the stability link for the size of the set. Run the set and adjust the voltage with the trimmer. Check the LED for under-speed or over-excitation.
Requesting a quotation for the STAMFORD AS480
Please send the generator type, the supply and the quantity. Seven Star LLC serves industrial customers in Oman and the GCC and replies with a quotation based on the information provided.
AS480 input
The sensing and power input is 100 to 264 V ac, single phase, 50 to 60 Hz.
AS480 output
The output is 82 V dc at 200 V ac input and 45 V dc at 110 V ac input.
AS480 output current
The output current is 5 A continuous and 7.5 A for 10 seconds.
AS480 regulation
The regulation is plus or minus 1.0 percent with 4 percent engine governing.
AS480 response
The AVR responds in 20 ms, and the machine voltage reaches 97 percent in 300 ms.
AS480 under-frequency protection
The set point is 94 to 98 percent, with a jumper for 50 or 60 Hz.
AS480 over-excitation protection
The set point is 67 V dc, plus or minus 3 percent, with a delay of 10 to 15 seconds.
AS480 temperature range
It works from minus 40 to plus 70 degrees C, with output derating above 60 degrees C.
Regulator records for the AS480
Record the link positions, the trimmer setting and the date of each test.
Choosing the right AS480 setting
Use the slow response setting on small sets, and the faster setting on larger machines.
Documents and quotation
Seven Star LLC supplies STAMFORD AVRs on request from Muscat. The specification, installation and adjustments datasheet is linked here. Send the alternator model and serial number from the nameplate and the existing AVR code, because the correct replacement depends on the excitation system. See Diesel Generator Spare Parts for more generator components, or the Cummins C150D5 150 kVA diesel generator set for a complete set. Confirm the version and any revision against the original unit before ordering.
Datasheets & Documents
- Datasheet STAMFORD AS480 AVR specification, installation and adjustments TD_AS480 (EN) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
STAMFORD, branded STAMFORD | AvK, is the alternator maker of Cummins Generator Technologies, building brushless AC alternators and automatic voltage regulators from 7.5 to 11,200 kVA. Its heritage runs back to 1904, when the Cutting Brothers started an electrical engineering business in Stamford, England. Seven Star LLC, an independent supplier in Muscat, sources these alternators and regulators for generator builders and plant owners in Oman and the GCC.
Alternators and AVRs listed here
The pages cover the S-Range alternators S0, S1, S4, S5, S6, S7K and S9LV, the UC22 and UC27 frames, and the AS480, MX321, MX341, MX342, SX460 and DM110 voltage regulators. Each page carries the ratings and specification from the maker brochure, datasheet or owner manual, including options as printed.
Where these alternators are used
The maker names data centres, marine, telecoms, standby and critical protection, combined heat and power, rail and prime power as typical applications, on diesel and gas engines. In the Gulf these are the same standby and prime-power sets used on camps, plants and pumping stations.
Ordering parts and alternators: what we need
For an alternator, send the model, serial number, winding number, kVA, voltage and frequency from the nameplate. For a regulator, send the code printed on the existing board and the alternator model, because the right replacement depends on the excitation system.
Related products
Frequently Asked Questions
5 A continuous and 7.5 A transient for 10 seconds, with 15 ohms minimum exciter resistance.
100 to 264 V ac, single phase, 50 to 60 Hz.
Plus or minus 1.0 percent, with 4 percent engine governing.
Yes, it has a quadrature droop CT input for parallel running with similarly equipped generators.
The Excitation Boost System, an external rotary supply providing excitation during heavy overloads and short circuits.